DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER Hydroseal® Diaphragm Version FKC...5 DATA SHEET FEATURES 1. Unique hydroseal diaphragm Permeation of hydrogen into the detecting unit through seal diaphragm can be suppressed thanks to the unique seal diaphragm (double coating) which employs coating of gold and ceramic. Micro Capacitance Silicone sensor Base material (SUS316L) Process cover Sensor unit Ceramics coating Gold coating [ L-Type ] Sealing diaphragm coated with gold and ceramics 2. High accuracy ±0.15% accuracy for all calibrated spans is the standard feature for differential pressure (flow) transmitter covering 0.32 to 130kPa (or 32mm to 13 mH2O). Fuji’s Micro-capacitance silicon sensor assures this feature. 3. Minimum environment influence Fuji’s patented “Advanced Floating Cell” design which protects the pressure sensor against changes in tempera-ture, static pressure, and overpressure substantially re-duces total measurement error in actual field applications. 4. Fuji/HART® bilingual communications protocol FCX–AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX–AIII. 5. Application flexibility Various options that render the FCX–AIII series suitable for almost any process applications include. − Full range of hazardous location approvals − 5-digit LCD meter with engineering unit − Stainless steel electronics housing − Built-in RFI filter and lightning arrester 6. Programmable output Linearization Function In addition to Linear and Square Root, output signal can be freely programmable. (Up to 14 compensated points at approximation.) 7. Burnout current flexibility (Under Scale: 3.2 to 4.0mA, Over Scale: 20.0 to 22.5mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator ( HHC ) to comply with NAMUR NE43. 8. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. [ T-Type ] SPECIFICATIONS Functional specifications Service: Liquid, gas, or vapour Static pressure, span, and range limit: Static pressure [MPa] {bar} Type F KC 33 F KC 35 −0.1 to 16 (−1 to + 160) −0.1 to 16 (−1 to + 160) Span limit [kPa] {mbar} Min. Max. 3.2 (32) 13 (130) 32 (320) 130) (1300) Range limit [KPa] {m bar} +/− 32 (+/− 320) +/− 130 (+/−1300) − Lower limit of static pressure (vacuum limit) ; Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at temperature below 60°C − The maximum span of each sensor can be converted to different units using below factors. 1MPa =10 3KPa=10bar=10.19716kgf/cm2 =145.0377psi 1kpa=10mbar=101.9716mmH2O=4.01463inH2O Overrange limit: To maximum static pressure limit Output signal: 4 to 20mA DC (linear or square root) with digital signal superimposed on the 4 to 20mA signal Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. EDSX6-135h Date Aug. 10, 2011 FKC...5 Load limitations: see figure below [Ω] Load resistance 2000 1474Ω 1500 R= E-10.5 (Imax+0.9)x10-3 1000 577Ω Operating area 500 24V 250 0 10 45V 16.35 10.5V Power voltage (DC) 50 E[ V ] Note: For communication with HHC (Model: FXW), min. of 250 required. Hazardous locations: (Under an application) See TABLE 2 Zero/span adjustment: Zero and span are adjustable from the HHC (1). Zero and span are also adjustable externally from the adjustment screw. Damping: Adjustable from HHC or local configurator unit with LCD display. The time constant is adjustable between 0.06 to 32 seconds. Zero elevation/suppression: ±100% to +100% of URL Normal/reverse action: Selectable from HHC (1) Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC (1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.0mA to 22.5mA from HHC (1) “Output Underscale”: Adjustable within the range 3.2mA to 4.0mA from HHC (1) 3.2 4 20 22.5 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout Probable over range Loop-check output: Transmitter can be configured to provide constant signal 3.2mA through 22.5mA by HHC (1). Temperature limit: Ambient: −40 to +85°C (−20 to +80°C for LCD indicator) (− 40 to +60°C for arrester option) (−10 to +60°C for fluorinated oil filled transmitters) For explosionproof units (fl ameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. (Note) 2 (1) HHC: Hand Held Communicator Process: −40 to +120°C for silicone fill sensor −20 to +80°C for fluorinated oil fill sensor Storage: −40 to +90°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following items can be remotely displayed or configured. Note: HHC’s version must be higher than 7.0 (or FXW 1− 4), for FCX–AIII. Local configurator with LCD display (option): Local confi gurator with 3 push button and LCD display can support following items. Items By communication By local configurator with FXW (with 3 push button) Display Set Display Set Tag No. v v v v Model No. v v v v Serial No. & Software Version v — v — Engineering unit v v v v Range limit v — v — Measuring range v v v v Damping v v v v Linear v v v v Square root v v v v Burnout direction v v v v Calibration v v v v Output adjust — v — v Data v — v — Output mode Self diagnoses v — v — Printer (In case of FXW with printer option) v — — — External switch lock v v v v Transmitter display v v v v Linearize v v — — Rerange v v v v Saturate current v v v v Write protect v v v v History – Calibration history – Ambient temperature history v v v — v v v — Programmable output linearization function: Output signal can be characterized with “14 points linear approximation function” from HHC (1). EMC Conformity: EN61326-1: 2006 Performance specifications for linear output Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4 to 20mA analog output in linear mode. Accuracy rating: (including linearity, hysteresis, and repeatability) Linear output : ±0.15% Square root output : 50 to 100% 0.15% 20 to 50% 0.375% 10 to 20% 0.75% Stability: ±0.15% of upper range limit (URL) for 10 years. Temperature effect: Effects per 28°C change between the limits of −40°C and +85°C Output Linear Zero shift Total effect URL ± 0.1+0.075 % Span ( ) Square root ( ± 0.125+0.075 ( ±2.5 × 0.125+0.075 URL % Span ) URL %/28°C x ) Static pressure effect: Zero shift (% of URL) : ±0.15% /10MPa {100bar} Overrange effect: Range code (6th digit in Code symbols) Zero shift (% of URL) “3” 1 % URL / 16MPa “5” 0.6 % URL / 16MPa Supply voltage effect: Less than 0.005% of calibrated span per 1V Update period: 60 msec *) Step response: (without electrical damping) Range code (6th digit in Code symbols) Time constant*) “3” 0.12 s “5” 0.08 s Dead time*) 0.12 s *) Faster response is available as option (maximum update rate: 25 times per second). Mounting position effect: Zero shift, less than 0.12kPa {1.2m bar} for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting Zero. Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100M at 500V DC. Internal resistance for external field indicator: 12 or less Low flow cut-off: In the case of square root output mode, customer configurable for any point between 0 to 20% of output. Physical specifications Electrical connections: G1/ 2, 1 / 2 -14 NPT, Pg13.5, or M20 × 1.5 conduit, as specified. Process connections: 1/ 4 -18 NPT or Rc1 / 4 on 54mm centers, as specified. Meets DIN 19213. Process-wetted parts material: l a i r e t aM e d o c t iProcess g i d h tcover 7( e d oC n i symbols) C 316 stainless steel(*1) Diaphragm Wetted sensor body 316L stainless 316 stainless steel(*2) steel Non-wetted parts material: Electronics housing: Low copper diecast aluminum alloy finished with polyester coating (standard), or 316 stainless steel ( SC S14 A per JIS G5121), as specified. Bolts and nuts: Cr-Mo alloy (standard), 304 stainless steel, or 630 stainless steel. Static pressure rating for code “3” with 304 stainless steel bolts is degraded to 10MPa. Fill fluid: Silicone oil (standard) or fluorinated oil Mounting bracket: 304 stainless steel, as specified Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm(JIS 50A) pipe using mounting bracket, direct wall mounting, or direct process mounting. Mass{weight}: Transmitter approximately 3.6kg without options. Add; 0.5kg for mounting bracket 4.5kg for stainless steel housing option Vent/drain 316/316L stainless steel Notes: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM A351/A351M) (*2) The diaphragm face is coated with gold and ceramic. Remark: Sensor O-rings: Viton O-ring and teflon gasket selectable. Optional features Indicator: A plug-in analog indicator (2.5% accuracy). An optional 5-digit LCD meter with engineering unit is also available. Local configurator with LCD display: An optional 5 digits LCD meter with 3 push buttons can support items as using communication with FXW. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity : 4kV (1.2 x 50µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: The fill fluid is flourinated oil. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. NACE specification: Metallic materials for all pressure boundary parts comply with NACE MR-01-75. ASTM B7M or L7M bolts and 2HM nuts (Class II) are available. Static pressure rating for code “3” (16 MPa) is degraded to 10MPa. Vacuum service: Special silicone oil and filling procedure are applied. See Fig. 1. Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/ polyurethane double coating. Specify if environment is extremely corrosive. 3 FKC...5 CODE SYMBOLS Digit 4 <Connection> Oval flange Process connection screw 7/16-20UNF Rc1/4 7/16-20UNF 1/4-18NPT 1/4-18NPT M10 1/4-18NPT M10 7/16-20UNF 1/4-18NPT 7/16-20UNF Rc1/4 7/16-20UNF 1/4-18NPT 1/4-18NPT M10 1/4-18NPT M10 7/16-20UNF 1/4-18NPT 5, 6, 7 <Span and materials> Span limit Static pressure [kPa] (mbar) [MPa] {bar} –0.1 to 16 3.2...32 (–1 to (32...320) +160) 13...130 (130...1300) 9 10 11 1 2 3 4 5 6 7 8 Note Description Conduit connection G1/2 1/2-14NPT Pg 13.5 M20×1.5 Pg 13.5 G1/2 1/2-14NPT Pg 13.5 M20×1.5 Pg 13.5 Process cover 9 10 11 12 13 5 Case type T type T type T type T type T type L type L type L type L type L type Diaphragm 5 6 7 8 9 S T V W X Wated cell body 316 stainles 316Lstainless 316 stainless Note 1 steel steel (*1) steel 33C Note 1 35C <Indicator and arrester> Indicator Arrester None None Analog, 0 to 100% linear scale None Analog, 0 to 100% sq. root scale None (*2) Analog, custom scale None Analog, double scale (Linear and sq. root) None None Yes Analog, 0 to 100% linear scale Yes Analog, 0 to 100% sq. root scale Yes (*2) Analog, custom scale Yes Analog, double scale (Linear and sq. root) Yes Digital, 0 to 100% linear scale None Digital, custom scale None Digital 0 to 100% square root None Digital, 0 to 100% linear scale Yes Digital, custom scale Yes Digital 0 to 100% square root Yes Digital, 0 to 100% linear scale (Local configurator unit with LCD display) None Digital, custom scale (Local configurator unit with LCD display) None Digital, 0 to 100% square root scale (Local configurator unit with LCD display) None Digital, 0 to 100% linear scale (Local configurator unit with LCD display) Yes Digital, custom scale (Local configurator unit with LCD display) Yes Digital, 0 to 100% square root scale (Local configurator unit with LCD display) Yes <Approvals for hazardous locations> None (for ordinary locations) TIIS, Flameproof (Cable gland seal) (*7) TIIS, Intrinsic safety FM, Flameproof (or explosionproof) (*10) FM, Intrinsic safety and nonincentive FM Combined of flameproof and intrinsic safety (*10) ATEX Flameproof (*9) ATEX Intrinsic safety ATEX Type n ATEX Combined of flameproof and intrinsic safety (*9) IECEx Scheme, Flameproof (*9) IECEx Scheme, Intrinsic safety CSA, Flameproof (or explosionproof) (*10) CSA, Intrinsic safety and nonincentive NEPSI, Flameproof (or exprosionproof) NEPSI, Intrinsic safety NEPSI, Combined of flameproof and intrinsic safety <Vent/ drain and mounting bracket> Vent/drain Mounting bracket Process connection Standard None Standard Standard Yes, SUS304 Standard Standard Yes, SUS316 Standard Side None Standard Side Yes, SUS304 Standard Side Yes, SUS316 Standard Note 1: (*1) The diaphragm face is coated with gold and ceramic. Note 2: (*2) In case of square root output mode, square root scale is not available. 4 F KC Note 2 Note 2 A B C D J E F G H K L P M Q S N 1 2 3 4 5 6 Note 7 Note 10 Note 10 Note 9 Note 9 Note 9 Note 10 A C G D H V X K P M R T E J F S U A C K D F L 14 15 21 Digit No. of code 1 2 3 4 5 6 7 8 Digit 12 Description Note F KC 9 10 11 12 13 <Options> Extra SS tag plate Stainless steel elec, housing Coating of cell Note 3 None None None Yes None None None None Yes (*3) Yes None Yes Note 11 None Yes Yes (*11) Note 11 Yes Yes Yes <Special applications and fill fluid> Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil NACE specification Silicone oil (Not available for 15th digit code “A”, “B”) <Sensor O-ring / Gasket> Teflon (gasket) <Bolt/nut> (*5) Vent Drain plug type Note 5 Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Standard Standard Cr-Mo alloy hexagon bolt/nut Note 4 Standard NACE bolt/nut (ASTM A193 B7M/A194 2HM) Standard NACE bolt/nut (ASTM A320 L7M/A194 2HM) (*4) Standard 304 stainless steel bolt/304 stainless steel nut Standard 316 stainless steel bolt/316 stainless steel nut Note 6 <Other options> (*6) Instruction manual unattached Opposite Vent/Drain Plug Position Instruction manual attached Opposite Vent/Drain Plug Position Instruction manual unattached 13 14 15 21 Note 3: Note 4: Note 5: Note 6: 14 15 21 5 Digit No. of code Y B M N P Q Y W G A N B A B C D E U L C P (*3) (*4) (*5) (*6) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. Static pressure should be −0.1 to +10MPa {−1 to +100bar}. In case of tropical use, select stainless bolts and nuts. If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. Note 7: (*7) Available for 4th digit code "S". Note 9: (*9) Available for 4th digit code "6", "8", "T", "W". Note 10: (*10) Available for 4th digit code "6", "T". Note 11: (*11) Not available for 10th digit code "C". Silicon oil (Code : Y. G. N) ACCESSORIES Oval flanges: [kPa abs] {mmHg abs} 101 {1010} Operating pressure Operating area 20 {200} 4 {40} 2.7 {27} Non-operating area –40 –15 60 85 120 [°C] Process temperature [°C] Fig. 1 Relation between process temperature and operating pressure ( Model FFP, refer to Data Sheet No. EDS6-128) Converts process connection to 1/2-14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel. Equalizing valves: (Model FFN, refer to Data Sheet No. EDS6-128) Available in CS or in 316 stainless steel and in pressure rating 16MPa or 42MPa. Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) ORDERING INFORMATION When ordering this instrument, specify: 1. CODE SYMBOLS 2. Measuring range 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale / Underscale Unless otherwise specified, output hold function is supplied. 4. Output mode (linear or square root output) Unless otherwise specified, output mode is linear. 5. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit). 6. Tag No. (up to 14 alphanumerical characters), if required. 5 FKC...5 OUTLINE DIAGRAM (Unit:mm) <AMP. case: L type> VENT/DRAIN PLUG (WHEN THE VENT/DRAIN PLUG ATTACHED ON THE UPPER SIDE OF THE DETECTOR) NOTE2) IN CASE OF 4TH DIGIT CODE "S,V,W,X" IN CASE OF 4TH DIGIT CODE "T" "A" PRESS. CONN. φ81 120 126 RO 38 "B" CONDUIT CONN. 57 37 (21) 4 HOLES 9 DIA. U-BOLT M8 8 41 ZERO 103 70 φ81 41 10 ZERO ADJ. SCREW 103 MTG. PIPE JIS 50A (2B) 198 WITH ANALOG IND. (11) 126 43 41 VENT/DRAIN PLUG WITH DIGITAL IND. EARTH TERMINAL DETAIL "A" (PRESS. CONN.) 2.5 φ18.5 DETAIL "B" (CONDUIT CONN.) φ15 SIDE VENT(OPTION) E F 41.3 8 224 H OVAL FLANGE SCREW SEE TABLE1 10 SEE TABLE1 SEE TABLE1 Conduit conn. H.P L.P D Press. conn. 4-M8×12 4th digit of the code symbols D E F H S G 1/2 18 2 Rc1/4 7/16-20UNF SCREW DEPTH15 T 1/2-14NPT 16 4 1/4-18NPT 7/16-20UNF SCREW DEPTH15 V Pg13.5 10.5 4.5 1/4-18NPT M10 SCREW DEPTH15 W M20×1.5 16 4 1/4-18NPT M10 SCREW DEPTH15 X Pg13.5 10.5 4.5 1/4-18NPT 7/16-20UNF SCREW DEPTH15 Oval frange screw 54 70 104 TABLE 1 OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) 10th digit code C (Cable gland type) NOTE1) DETAIL C φ13 −/CK− CK+ 19 106 17 75 + G1/2 φ33.5 CONNECTION DIAGRAM <SS TAG PLATE> "C" CONDUIT CONN. G1/2 20 CABLE GLAND NOTE1) IN CASE OF 10TH CODE“C” , φ11 CABLE IS SUITBLE. NOTE2) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS ATTACHED ON THE UPPER SIDE OF THE DETECTOR (WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P). 6 <AMP. case: T type> VENT/DRAIN PLUG (WHEN THE VENT/DRAIN PLUG ATTACHED ON THE UPPER SIDE OF THE DETECTOR) NOTE2) WITH DIGITAL IND. IN CASE OF 4TH DIGIT CODE "5,7,8,9" (21) (11) 8 EARTH TERMINAL 41 "A" PRESS. CONN. 10 MTG. PIPE JIS 50A (2B) WITH ANALOG IND. IN CASE OF 4TH DIGIT CODE "6" ZERO ADJ. SCREW U-BOLT M8 φ81 127 70 100 ZERO 38 "B" CONDUIT CONN. 37 57 194 17 127 4 HOLES 9 DIA. 20 VENT/DRAIN PLUG DETAIL "A" (PRESS. CONN.) DETAIL "B" (CONDUIT CONN.) OVAL FLANGE SCREW SEE TABLE1 φ15 SIDE VENT(OPTION) E 41.3 F 8 H 10 251 2.5 φ18.5 D H.P L.P SEE TABLE1 SEE TABLE1 4-M8×12 Conduit conn. Press. conn. 4th digit of the code symbols D E F H 5 G 1/2 18 2 Rc1/4 7/16-20UNF SCREW DEPTH15 6 1/2-14NPT 16 4 1/4-18NPT 7/16-20UNF SCREW DEPTH15 7 Pg13.5 10.5 4.5 1/4-18NPT M10 SCREW DEPTH15 8 M20×1.5 16 4 1/4-18NPT M10 SCREW DEPTH15 9 Pg13.5 10.5 4.5 1/4-18NPT 7/16-20UNF SCREW DEPTH15 Oval frange screw 54 70 104 TABLE 1 CONNECTION DIAGRAM −/CK− CK+ 75 + <SS TAG PLATE> 20 NOTE2) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS ATTACHED ON THE UPPER SIDE OF THE DETECTOR (WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P). 7 FKC...5 TABLE 2 Authorities ATEX Intrinsic safety Authorities Ex II 1 G Ex ia IIC T5 Tamb = –40°C to +50°C Ex ia IIC T4 Tamb = –40°C to +70°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) Factory Mutual 13th digit Y,G,N Y,G,N Y,G,N Y,G,N W,A Tamb Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C CSA Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Note) “Seal Not Required” enclosure is allowed. Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester), Ci=36nF (With Arrester),Li=0.6mH (Without analog meter), Li=0.7mH (With analog meter) TIIS Ex do IIB+H2 T4 Tamb max = +60°C Maximum process temp. = +120°C IECEx Scheme Ex d IIC T5 IP66/67 Tamb = −40°C to +85°C Ex d IIC T6 IP66/67 Tamb = −40°C to +65°C NEPSI Ex d IIB+H2 T6 Tamb = −40°C to +60°C Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=38.4nF, Li=0.694mH IECEx Scheme Ex ia IIC T4 Tamb = –40°C to +70°C Ex ia IIC T5 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) 13th digit Y,G,N Y,G,N Y,G,N Y,G,N W,A Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Factory Mutual (pending) Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 9th digit A,B,C,D,J L,P,M,1,2,3 Q,S,N,4,5,6 E,F,G,H,K – Entity Parameters: Ui=42.4V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH CSA Caution on Safety Ex II 3 GD EEx nL IIC T5 Tamb = −40°C to +50°C EEx nL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=25.18nF, Li=0.694mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH EEx nAL IIC T5 Tamb = −40°C to +50°C EEx nAL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Ex ia IIC T4 Ex d IIB+H2 T6 / Ex ia IIC T4 Model code 9th digit A,B,C,D,J L,P,M,1,2,3 Q,S,N,4,5,6 E,F,G,H,K – Type n Nonincendive Authorities ATEX TIIS NEPSI Ex II 2 GD Ex d IIC T6 IP66/67 T85°C Tamb = −40°C to +65°C Ex d IIC T5 IP66/67 T100C Tamb = −40°C to +85°C −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Entity Parameters: Vmax=28V, Imax=94.3mA, Pi=0.66W, Ci=35.98nF, Li=0.694mH CSA ATEX Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 9th digit A,B,C,D,J L,P,M,1,2,3 Q,S,N,4,5,6 E,F,G,H,K – Flameproof 13th digit Y,G,N Y,G,N Y,G,N Y,G,N W,A Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Ci=25.18nF (Without Arrester), Ci=35.98nF (With Arrester), Li=0.694mH *Before using this product, be sure to read its instruction manual in advance. International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice. Printed in Japan