FUJI EDSX6-135H

DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER
Hydroseal® Diaphragm Version
FKC...5
DATA SHEET
FEATURES
1. Unique hydroseal diaphragm
Permeation of hydrogen into the detecting unit through
seal diaphragm can be suppressed thanks to the unique
seal diaphragm (double coating) which employs coating
of gold and ceramic.
Micro Capacitance
Silicone sensor
Base material
(SUS316L)
Process
cover
Sensor
unit
Ceramics
coating
Gold
coating
[ L-Type ]
Sealing diaphragm
coated with gold
and ceramics
2. High accuracy
±0.15% accuracy for all calibrated spans is the standard feature for differential pressure (flow) transmitter
covering 0.32 to 130kPa (or 32mm to 13 mH2O). Fuji’s
Micro-capacitance silicon sensor assures this feature.
3. Minimum environment influence
Fuji’s patented “Advanced Floating Cell” design which
protects the pressure sensor against changes in tempera-ture, static pressure, and overpressure substantially re-duces total measurement error in actual field
applications.
4. Fuji/HART® bilingual communications protocol
FCX–AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX–AIII.
5. Application flexibility
Various options that render the FCX–AIII series suitable
for almost any process applications include.
− Full range of hazardous location approvals
− 5-digit LCD meter with engineering unit
− Stainless steel electronics housing
− Built-in RFI filter and lightning arrester
6. Programmable output Linearization Function
In addition to Linear and Square Root, output signal can
be freely programmable.
(Up to 14 compensated points at approximation.)
7. Burnout current flexibility (Under Scale: 3.2 to
4.0mA, Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator ( HHC ) to comply with
NAMUR NE43.
8. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as
wet calibration.
[ T-Type ]
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Static pressure
[MPa] {bar}
Type
F KC
33
F KC
35
−0.1 to 16
(−1 to + 160)
−0.1 to 16
(−1 to + 160)
Span limit [kPa]
{mbar}
Min.
Max.
3.2
(32)
13
(130)
32
(320)
130)
(1300)
Range limit
[KPa] {m bar}
+/− 32
(+/− 320)
+/− 130
(+/−1300)
− Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor:
See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs)
at temperature below 60°C
− The maximum span of each sensor can be converted
to different units using below factors.
1MPa =10 3KPa=10bar=10.19716kgf/cm2
=145.0377psi
1kpa=10mbar=101.9716mmH2O=4.01463inH2O
Overrange limit: To maximum static pressure limit
Output signal:
4 to 20mA DC (linear or square root)
with digital signal superimposed on the
4 to 20mA signal
Power supply:
Transmitter operates on 10.5V to 45V
DC at transmitter terminals.
10.5V to 32V DC for the units with optional arrester.
EDSX6-135h
Date
Aug. 10, 2011
FKC...5
Load limitations: see figure below
[Ω]
Load resistance
2000
1474Ω
1500
R=
E-10.5
(Imax+0.9)x10-3
1000
577Ω
Operating
area
500
24V
250
0
10
45V
16.35
10.5V
Power voltage (DC)
50
E[ V ]
Note: For communication with HHC (Model: FXW), min. of 250 required.
Hazardous locations: (Under an application) See TABLE 2
Zero/span adjustment:
Zero and span are adjustable from the
HHC (1). Zero and span are also adjustable externally from the adjustment
screw.
Damping:
Adjustable from HHC or local configurator
unit with LCD display.
The time constant is adjustable between
0.06 to 32 seconds.
Zero elevation/suppression:
±100% to +100% of URL
Normal/reverse action:
Selectable from HHC (1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC (1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just
before failure happens.
“Output Overscale”:
Adjustable within the range 20.0mA to
22.5mA from HHC (1)
“Output Underscale”:
Adjustable within the range 3.2mA to
4.0mA from HHC (1)
3.2
4
20
22.5 [mA]
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.2mA through 22.5mA
by HHC (1).
Temperature limit:
Ambient: −40 to +85°C
(−20 to +80°C for LCD indicator)
(− 40 to +60°C for arrester option)
(−10 to +60°C for fluorinated oil filled
transmitters)
For explosionproof units (fl ameproof
or intrinsic safety), ambient temperature must be within the limits specified in each standard.
(Note)
2
(1) HHC: Hand Held Communicator
Process: −40 to +120°C for silicone fill
sensor
−20 to +80°C for fluorinated oil fill
sensor
Storage: −40 to +90°C
Humidity limit: 0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following items can
be remotely displayed or configured.
Note: HHC’s version must be higher than 7.0
(or FXW
1− 4), for FCX–AIII.
Local configurator with LCD display (option):
Local confi gurator with 3 push button
and LCD display can support following
items.
Items
By communication By local configurator
with FXW
(with 3 push button)
Display
Set
Display
Set
Tag No.
v
v
v
v
Model No.
v
v
v
v
Serial No. & Software Version
v
—
v
—
Engineering unit
v
v
v
v
Range limit
v
—
v
—
Measuring range
v
v
v
v
Damping
v
v
v
v
Linear
v
v
v
v
Square root
v
v
v
v
Burnout direction
v
v
v
v
Calibration
v
v
v
v
Output adjust
—
v
—
v
Data
v
—
v
—
Output mode
Self diagnoses
v
—
v
—
Printer (In case of FXW with
printer option)
v
—
—
—
External switch lock
v
v
v
v
Transmitter display
v
v
v
v
Linearize
v
v
—
—
Rerange
v
v
v
v
Saturate current
v
v
v
v
Write protect
v
v
v
v
History
– Calibration history
– Ambient temperature history
v
v
v
—
v
v
v
—
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation function” from HHC (1).
EMC Conformity: EN61326-1: 2006
Performance specifications for linear output
Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4
to 20mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
Linear output : ±0.15%
Square root output : 50 to 100%
0.15%
20 to 50%
0.375%
10 to 20%
0.75%
Stability:
±0.15% of upper range limit (URL) for
10 years.
Temperature effect:
Effects per 28°C change between the
limits of −40°C and +85°C
Output
Linear
Zero shift
Total effect
URL
± 0.1+0.075
%
Span
(
)
Square root
(
± 0.125+0.075
(
±2.5 × 0.125+0.075
URL
%
Span
)
URL
%/28°C
x
)
Static pressure effect:
Zero shift (% of URL) : ±0.15% /10MPa
{100bar}
Overrange effect:
Range code
(6th digit in Code symbols)
Zero shift (% of URL)
“3”
1 % URL / 16MPa
“5”
0.6 % URL / 16MPa
Supply voltage effect:
Less than 0.005% of calibrated span
per 1V
Update period: 60 msec *)
Step response: (without electrical damping)
Range code
(6th digit in Code symbols)
Time constant*)
“3”
0.12 s
“5”
0.08 s
Dead time*)
0.12 s
*) Faster response is available as option (maximum update rate: 25
times per second).
Mounting position effect:
Zero shift, less than 0.12kPa {1.2m bar}
for a 10° tilt in any plane.
No effect on span.
This error can be corrected by adjusting
Zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit and earth.
Insulation resistance:
More than 100M at 500V DC.
Internal resistance for external field indicator:
12 or less
Low flow cut-off: In the case of square root output mode,
customer configurable for any point
between 0 to 20% of output.
Physical specifications
Electrical connections:
G1/ 2, 1 / 2 -14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
Process connections:
1/ 4 -18 NPT or Rc1 / 4 on 54mm centers,
as specified.
Meets DIN 19213.
Process-wetted parts material:
l a i r e t aM
e d o c
t iProcess
g i d h tcover
7(
e d oC n i
symbols)
C
316 stainless
steel(*1)
Diaphragm
Wetted
sensor body
316L stainless 316 stainless
steel(*2)
steel
Non-wetted parts material:
Electronics housing: Low copper diecast aluminum alloy finished with
polyester coating (standard), or 316
stainless steel ( SC S14 A per JIS
G5121), as specified.
Bolts and nuts: Cr-Mo alloy (standard),
304 stainless steel, or 630 stainless
steel. Static pressure rating for code
“3” with 304 stainless steel bolts is
degraded to 10MPa.
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting bracket: 304 stainless steel,
as specified
Environmental protection:
IEC IP67 and NEMA 6/6P
Mounting:
On 60.5mm(JIS 50A) pipe using mounting bracket, direct wall mounting, or
direct process mounting.
Mass{weight}:
Transmitter approximately 3.6kg without
options.
Add; 0.5kg for mounting bracket
4.5kg for stainless steel housing
option
Vent/drain
316/316L
stainless steel
Notes: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM
A351/A351M)
(*2) The diaphragm face is coated with gold and ceramic.
Remark:
Sensor O-rings: Viton O-ring and teflon gasket selectable.
Optional features
Indicator:
A plug-in analog indicator (2.5% accuracy).
An optional 5-digit LCD meter with engineering unit is also available.
Local configurator with LCD display:
An optional 5 digits LCD meter with 3
push buttons can support items as using
communication with FXW.
Arrester:
A built-in arrester protects the electronics from lightning surges.
Lightning surge immunity : 4kV (1.2 x
50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all
process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: The fill fluid is flourinated oil.
Degreasing:
Process-wetted parts are cleaned, but
the fill fluid is standard silicone oil. Not
for use on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
ASTM B7M or L7M bolts and 2HM nuts
(Class II) are available.
Static pressure rating for code “3” (16
MPa) is degraded to 10MPa.
Vacuum service: Special silicone oil and filling procedure
are applied.
See Fig. 1.
Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/
polyurethane double coating. Specify if
environment is extremely corrosive.
3
FKC...5
CODE SYMBOLS
Digit
4
<Connection>
Oval flange
Process
connection screw
7/16-20UNF
Rc1/4
7/16-20UNF
1/4-18NPT
1/4-18NPT
M10
1/4-18NPT
M10
7/16-20UNF
1/4-18NPT
7/16-20UNF
Rc1/4
7/16-20UNF
1/4-18NPT
1/4-18NPT
M10
1/4-18NPT
M10
7/16-20UNF
1/4-18NPT
5, 6, 7 <Span and materials>
Span limit
Static
pressure [kPa]
(mbar)
[MPa]
{bar}
–0.1 to 16 3.2...32
(–1 to
(32...320)
+160)
13...130
(130...1300)
9
10
11
1 2 3 4 5 6 7 8
Note
Description
Conduit
connection
G1/2
1/2-14NPT
Pg 13.5
M20×1.5
Pg 13.5
G1/2
1/2-14NPT
Pg 13.5
M20×1.5
Pg 13.5
Process
cover
9 10 11 12 13
5
Case type
T type
T type
T type
T type
T type
L type
L type
L type
L type
L type
Diaphragm
5
6
7
8
9
S
T
V
W
X
Wated
cell body
316 stainles 316Lstainless 316 stainless
Note 1
steel
steel (*1)
steel
33C
Note 1
35C
<Indicator and arrester>
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, 0 to 100% sq. root scale
None (*2)
Analog, custom scale
None
Analog, double scale (Linear and sq. root)
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, 0 to 100% sq. root scale
Yes (*2)
Analog, custom scale
Yes
Analog, double scale (Linear and sq. root)
Yes
Digital, 0 to 100% linear scale
None
Digital, custom scale
None
Digital 0 to 100% square root
None
Digital, 0 to 100% linear scale
Yes
Digital, custom scale
Yes
Digital 0 to 100% square root
Yes
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
None
Digital, custom scale
(Local configurator unit with LCD display)
None
Digital, 0 to 100% square root scale
(Local configurator unit with LCD display)
None
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
Yes
Digital, custom scale
(Local configurator unit with LCD display)
Yes
Digital, 0 to 100% square root scale
(Local configurator unit with LCD display)
Yes
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Cable gland seal) (*7)
TIIS, Intrinsic safety
FM, Flameproof (or explosionproof) (*10)
FM, Intrinsic safety and nonincentive
FM Combined of flameproof and intrinsic safety (*10)
ATEX Flameproof (*9)
ATEX Intrinsic safety
ATEX Type n
ATEX Combined of flameproof and intrinsic safety (*9)
IECEx Scheme, Flameproof (*9)
IECEx Scheme, Intrinsic safety
CSA, Flameproof (or explosionproof) (*10)
CSA, Intrinsic safety and nonincentive
NEPSI, Flameproof (or exprosionproof)
NEPSI, Intrinsic safety
NEPSI, Combined of flameproof and intrinsic safety
<Vent/ drain and mounting bracket>
Vent/drain
Mounting bracket
Process connection
Standard
None
Standard
Standard
Yes, SUS304
Standard
Standard
Yes, SUS316
Standard
Side
None
Standard
Side
Yes, SUS304
Standard
Side
Yes, SUS316
Standard
Note 1: (*1) The diaphragm face is coated with gold and ceramic.
Note 2: (*2) In case of square root output mode, square root scale is not available.
4
F KC
Note 2
Note 2
A
B
C
D
J
E
F
G
H
K
L
P
M
Q
S
N
1
2
3
4
5
6
Note 7
Note 10
Note 10
Note 9
Note 9
Note 9
Note 10
A
C
G
D
H
V
X
K
P
M
R
T
E
J
F
S
U
A
C
K
D
F
L
14 15
21
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
12
Description
Note
F KC
9 10 11 12 13
<Options>
Extra SS tag plate
Stainless steel elec, housing
Coating of cell
Note 3
None
None
None
Yes
None
None
None
None
Yes
(*3)
Yes
None
Yes
Note 11
None
Yes
Yes
(*11)
Note 11
Yes
Yes
Yes
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Standard
Fluorinated oil
Degreasing
Silicone oil
Oxygen service Fluorinated oil
NACE specification Silicone oil (Not available for 15th digit code “A”, “B”)
<Sensor O-ring / Gasket>
Teflon (gasket)
<Bolt/nut> (*5)
Vent Drain plug type Note 5
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Standard
Standard
Cr-Mo alloy hexagon bolt/nut
Note 4
Standard
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
Standard
NACE bolt/nut (ASTM A320 L7M/A194 2HM)
(*4)
Standard
304 stainless steel bolt/304 stainless steel nut
Standard
316 stainless steel bolt/316 stainless steel nut
Note 6
<Other options> (*6)
Instruction manual unattached
Opposite Vent/Drain Plug Position
Instruction manual attached
Opposite Vent/Drain Plug Position
Instruction manual unattached
13
14
15
21
Note 3:
Note 4:
Note 5:
Note 6:
14 15
21
5
Digit No.
of code
Y
B
M
N
P
Q
Y
W
G
A
N
B
A
B
C
D
E
U
L
C
P
(*3)
(*4)
(*5)
(*6)
Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”.
Static pressure should be −0.1 to +10MPa {−1 to +100bar}.
In case of tropical use, select stainless bolts and nuts.
If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
Note 7: (*7) Available for 4th digit code "S".
Note 9: (*9) Available for 4th digit code "6", "8", "T", "W".
Note 10: (*10) Available for 4th digit code "6", "T".
Note 11: (*11) Not available for 10th digit code "C".
Silicon oil (Code : Y. G. N)
ACCESSORIES
Oval flanges:
[kPa abs]
{mmHg abs}
101
{1010}
Operating pressure
Operating
area
20
{200}
4
{40}
2.7
{27}
Non-operating
area
–40 –15
60 85 120 [°C]
Process temperature [°C]
Fig. 1 Relation between process temperature and
operating pressure
( Model FFP, refer to Data Sheet No.
EDS6-128)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in
316 stainless steel.
Equalizing valves:
(Model FFN, refer to Data Sheet No.
EDS6-128)
Available in CS or in 316 stainless steel
and in pressure rating 16MPa or 42MPa.
Hand-held communicator:
(Model FXW, refer to Data Sheet No.
EDS 8-47)
ORDERING INFORMATION
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality
is occurred in the transmitter.
Hold / Overscale / Underscale
Unless otherwise specified, output hold function is supplied.
4. Output mode (linear or square root output)
Unless otherwise specified, output mode is linear.
5. Indication method (indicated value and unit) in case of
the actual scale (code D, H, P, S on 9th digit).
6. Tag No. (up to 14 alphanumerical characters), if required.
5
FKC...5
OUTLINE DIAGRAM (Unit:mm)
<AMP. case: L type>
VENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG
ATTACHED ON THE UPPER SIDE
OF THE DETECTOR) NOTE2)
IN CASE OF 4TH DIGIT CODE "S,V,W,X"
IN CASE OF 4TH DIGIT CODE "T"
"A" PRESS. CONN.
φ81
120
126
RO
38
"B" CONDUIT CONN.
57
37
(21)
4 HOLES 9 DIA.
U-BOLT M8
8
41
ZERO
103
70
φ81
41
10
ZERO ADJ. SCREW
103
MTG. PIPE JIS 50A (2B)
198
WITH ANALOG IND.
(11)
126
43
41
VENT/DRAIN PLUG
WITH DIGITAL IND.
EARTH TERMINAL
DETAIL "A"
(PRESS. CONN.)
2.5
φ18.5
DETAIL "B"
(CONDUIT CONN.)
φ15
SIDE VENT(OPTION)
E
F
41.3
8
224
H
OVAL FLANGE SCREW
SEE TABLE1
10
SEE TABLE1
SEE TABLE1
Conduit conn.
H.P
L.P
D
Press. conn.
4-M8×12
4th digit of the
code symbols
D
E
F
H
S
G 1/2
18
2
Rc1/4
7/16-20UNF
SCREW DEPTH15
T
1/2-14NPT
16
4
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
V
Pg13.5
10.5
4.5
1/4-18NPT
M10
SCREW DEPTH15
W
M20×1.5
16
4
1/4-18NPT
M10
SCREW DEPTH15
X
Pg13.5
10.5
4.5
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
Oval frange screw
54
70
104
TABLE 1
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
10th digit code C (Cable gland type)
NOTE1)
DETAIL C
φ13
−/CK− CK+
19
106
17
75
+
G1/2
φ33.5
CONNECTION DIAGRAM
<SS TAG PLATE>
"C" CONDUIT CONN.
G1/2
20
CABLE GLAND
NOTE1) IN CASE OF 10TH CODE“C”
, φ11 CABLE IS SUITBLE.
NOTE2) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P).
6
<AMP. case: T type>
VENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG
ATTACHED ON THE UPPER SIDE
OF THE DETECTOR) NOTE2)
WITH DIGITAL IND.
IN CASE OF 4TH DIGIT CODE "5,7,8,9"
(21)
(11)
8
EARTH TERMINAL
41
"A" PRESS. CONN.
10
MTG. PIPE JIS 50A (2B)
WITH ANALOG IND.
IN CASE OF 4TH DIGIT CODE "6"
ZERO ADJ. SCREW
U-BOLT M8
φ81
127
70
100
ZERO
38
"B" CONDUIT CONN.
37
57
194
17
127
4 HOLES 9 DIA.
20
VENT/DRAIN PLUG
DETAIL "A"
(PRESS. CONN.)
DETAIL "B"
(CONDUIT CONN.)
OVAL FLANGE SCREW
SEE TABLE1
φ15
SIDE VENT(OPTION)
E
41.3
F
8
H
10
251
2.5
φ18.5
D
H.P
L.P
SEE TABLE1
SEE TABLE1
4-M8×12
Conduit conn.
Press. conn.
4th digit of the
code symbols
D
E
F
H
5
G 1/2
18
2
Rc1/4
7/16-20UNF
SCREW DEPTH15
6
1/2-14NPT
16
4
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
7
Pg13.5
10.5
4.5
1/4-18NPT
M10
SCREW DEPTH15
8
M20×1.5
16
4
1/4-18NPT
M10
SCREW DEPTH15
9
Pg13.5
10.5
4.5
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
Oval frange screw
54
70
104
TABLE 1
CONNECTION DIAGRAM
−/CK− CK+
75
+
<SS TAG PLATE>
20
NOTE2) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P).
7
FKC...5
TABLE 2
Authorities
ATEX
Intrinsic safety
Authorities
Ex II 1 G
Ex ia IIC T5 Tamb = –40°C to +50°C
Ex ia IIC T4 Tamb = –40°C to +70°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
Factory
Mutual
13th digit
Y,G,N
Y,G,N
Y,G,N
Y,G,N
W,A
Tamb
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Note) “Seal Not Required” enclosure is allowed.
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester),
Ci=36nF (With Arrester),Li=0.6mH (Without analog meter),
Li=0.7mH (With analog meter)
TIIS
Ex do IIB+H2 T4
Tamb max = +60°C
Maximum process temp. = +120°C
IECEx
Scheme
Ex d IIC T5 IP66/67
Tamb = −40°C to +85°C
Ex d IIC T6 IP66/67
Tamb = −40°C to +65°C
NEPSI
Ex d IIB+H2 T6
Tamb = −40°C to +60°C
Ex ia IIC T4
Tamb max = +60°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=38.4nF, Li=0.694mH
IECEx
Scheme
Ex ia IIC T4
Tamb = –40°C to +70°C
Ex ia IIC T5
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
13th digit
Y,G,N
Y,G,N
Y,G,N
Y,G,N
W,A
Tamb
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Factory
Mutual
(pending)
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,C,D,J
L,P,M,1,2,3
Q,S,N,4,5,6
E,F,G,H,K
–
Entity Parameters:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
CSA
Caution on Safety
Ex II 3 GD
EEx nL IIC T5 Tamb = −40°C to +50°C
EEx nL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=25.18nF, Li=0.694mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
EEx nAL IIC T5 Tamb = −40°C to +50°C
EEx nAL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Ex ia IIC T4
Ex d IIB+H2 T6 / Ex ia IIC T4
Model code
9th digit
A,B,C,D,J
L,P,M,1,2,3
Q,S,N,4,5,6
E,F,G,H,K
–
Type n
Nonincendive
Authorities
ATEX
TIIS
NEPSI
Ex II 2 GD
Ex d IIC T6 IP66/67 T85°C
Tamb = −40°C to +65°C
Ex d IIC T5 IP66/67 T100C
Tamb = −40°C to +85°C
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Pi=0.66W,
Ci=35.98nF, Li=0.694mH
CSA
ATEX
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,C,D,J
L,P,M,1,2,3
Q,S,N,4,5,6
E,F,G,H,K
–
Flameproof
13th digit
Y,G,N
Y,G,N
Y,G,N
Y,G,N
W,A
Tamb
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Ci=25.18nF (Without Arrester),
Ci=35.98nF (With Arrester), Li=0.694mH
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan