Model Z - Honeywell Test and Measurement Sensors

Model Z
High Range Wet/Wet Differential
Pressure Transducer
DESCRIPTION
The Z High Range Wet/Wet transducers are engineered to
A variety of standard options are available with the Model Z in-
measure differential pressures as great as 10k psid and achieve
cluding choice of pressure adaptors, alternative pressure ports,
accuracy of 0.25 % full scale. Each is bi-directional and accepts
internal amplifiers options, and electrical terminations.
fluid in both ports. 17-4 PH stainless steel ensures durability of
these bonded foil strain gage units under harsh industrial conditions.
FEATURES
• 0.25% accuracy
• 2000 psid to 10000 psid
•
mV/V (standard), 4 mA to 20 mA, 0 Vdc to 5 Vdc, or 0 Vdc
to 10 Vdc output
• Intrinsically safe available (2N option only)10
• CE approved11
Model Z
PERFORMANCE SPECIFICATIONS
Characteristic
Measure
Pressure ranges
2000, 3000, 5000, 7500, 10000 psid
Accuracy
±0.25 % full scale
Linearity
±0.15 % full scale (typical)
Hysteresis
±0.10 % full scale (typical)
Non-repeatability
±0.05 % full scale (typical)
Output (standard)
2 mV/V (nominal)
Line pressure
2000 psi
Resolution
Infinite
ENVIRONMENTAL SPECIFICATIONS
Characteristic
Measure
Temperature, operating
-54 °C to 121 °C [-65 °F to 250 °F]
Temperature, compensated
15 °C to 71 °C [60 °F to 160 °F]
Temperature, effect, zero
±0.5 % full scale/100 °F
Temperature, effect, span
±0.5 % reading/100 °F
ELECTRICAL SPECIFICATIONS
Characteristic
Measure
Strain gage type
Bonded foil
Excitation (calibration)
10 Vdc
Bridge resistance
350 ohm (nominal)
Shunt calibration data
Included
Elec. termination (std)
PTIH-10-6P or equivalent (hermetic
stainless)
Mating connector (not incl.)
PT06A-10-6S or equiv. (AA111)
MECHANICAL SPECIFICATIONS
Characteristic
Measure
Media
Gas, liquid
Overload-safe
number here
2000 psid to 3000 psid
100% over capacity
5000 psid to 10000 psid
50% over capacity
Pressure port
1/4-18 NPT female (2)
Wetted parts material
17-4 PH stainless steel
Case material
Stainless steel
2 Honeywell • Sensing and Control
OPTION CODES
Range Code
Pressure ranges
(psid)
Many range/option combinations are available in
our quick-ship and fast-track manufacture programs.
Please see http://sensing.honeywell.com/TMsensorship for updated listings.
2000, 3000, 5000, 7500, 10000
Temperature
compensation
1a. 60 °F to 160 °F
1b. 30 °F to 130 °F
1c. 0 °F to 185 °F
1d. -20 °F to 130 °F
1e. -20 °F to 200 °F
1f. 70 °F to 250 °F
1g. 70 °F to 325 °F6
1h. 70 °F to 400 °F6
1i. -65 °F to 250 °F6
1j. 0 °C to 50 °C
1m. -25 °C to 110 °C
Internal
amplifiers
2u. Unamplified,
mV/V output
2b. 4 wire ±5 Vdc
2c. 0 Vdc to 5 Vdc
2t. 0 Vdc to 10 Vdc
2j. 4 mA to 20 mA
(three-wire) output
2k. 4 mA to 20 mA
(two-wire) output12
2n. (2N) 4 mA to 20
mA (two-wire)
intrinsically safe12
Pressure ports 5
5a. 1/4-18 NPT female
5c. 7/16-20 UNF female
Electrical
termination
6a. Bendix PTIH-10-6P
(or equiv.) 6 pin
(max. 250 °F)
6b. MS type connector to mate with
MS3106-14S-6S
(max. 160 °F)1
6e. Integral cable:
Teflon (-54 °C to
245 °C)
6f. Integral cable: PVC
(-30 °C to 70 °C)
Shunt
calibration
8a. Precision internal resistor8
Special
calibration
9a. 10 point (5 up/5 down) 20% increments @ 20 °C
9b. 20 point (10 up/10 down) 10% increments @ 20 °C
Wetted
diaphragm
17-4 PH stainless steel
Bridge type
11a. Square bridge6
11c. Square & symmetrical bridge6
11b. Symmetrical bridge6
Zero and
span adjustment
14b. Top access to pots 7
14a. No access to pots
O ring seals
26a. Metal
Interfaces
53e. Signature calibration6
53t. TEDS IEEE 1451.4 module9
6g. Integral cable:
Neoprene (-20 °C
to 80 °C)1
6h. Integral cable:
Silicone (-54 °C to
150 °C)
6i. Integral underwater
cable (8m [26 ft])
(max. 80 °C)1
6j. 1/2-14 conduit fitting with 1,5 m [5 ft]
of 4 conductor PVC
cable
High Range Wet/Wet Differential Pressure Transducer
iNTERNAL AMPLIFIERS
Voltage output: Voltage output: Voltage output:
Option 2b
Option 2c
Option 2t
Current
three-wire:
Option 2j
Current
two-wire:
Option 2k
Intrinsically safe
amp: Option
2n (2N)***
Output signal
±5 V
0 V to 5 V or
±5 V @ 5 mA
0 V to 10 V or ±10
V @ 5 mA
4 mA to 20 mA
4 mA to 20 mA
4 mA to 20 mA
Input power (voltage)
±15 V or 26 Vdc
to 32 Vdc
11 Vdc to 28 Vdc
15 Vdc to 28 Vdc
22 Vdc to 32 Vdc
9 Vdc to 32 Vdc
9 Vdc to 28 Vdc
Input power (current)
45 mA
40 mA
40 mA
65 mA
4 mA to 28 mA
4 mA to 24 mA
Freq. resp (amp)
3000 Hz
3000 Hz
3000 Hz
2500 Hz
300 Hz
2000 Hz
Power supply rej.
60 db
60 db
60 db
60 db
60 db
60 db
Operating temp.
-20 °F to 185 °F
-20 °F to 185 °F
-20 °F to 185 °F
0 °F to 185 °F
0 °F to 185 °F
-20 °F to 185 °F
Reverse voltage
protection
Yes
Yes
Yes
Yes
Yes
Yes
Short cir. protection
Momentary
Momentary
Momentary
Yes
Yes
Yes
Wiring code:
connector (std)2
A (+) Supply
B Output common
C Supply return
D (+) Output
E Shunt cal 1
F Shunt cal 2
A (+) Supply
B Output common**
C Supply return **
D (+) Output
E Shunt cal 1
F Shunt cal 2
A (+) Supply
B Output common**
C Supply return**
D (+) Output
E Shunt cal 1
F Shunt cal 2
A (+) Supply
B Output common**
C Supply return**
D (+) Output
E Shunt cal 1
F Shunt cal 2
A (+) Supply
B No connection
C No connection
D (+) Output
E Case ground
F No connection
A (+) Supply
B No connection
C No connection
D (+) Output
E Case ground
F No connection
Wiring code: cable2,3,4
R (+) Supply
Bl Output common
G Supply return
W (+) Output
B Shunt cal 1
Br Shunt cal 2
R (+) Supply
Bl Output common*
G Supply return*
W (+) Output
B Shunt cal 1
Br Shunt cal 2
R (+) Supply
Bl Output common*
G Supply return*
W (+) Output
B Shunt cal 1
Br Shunt cal 2
R (+) Supply
Bl Output common*
G Supply return*
W (+) Output
B Shunt cal 1
Br Shunt cal 2
R (+) Supply
Bl (+) Output
W Case ground
R (+) Supply
Bl (+) Output
W Case ground
Amplifier
specifications
* Black and green wires are internally connected.
** Pins B and C are internally connected.
Mounting dimensions and characteristics
2X
Typical system diagram
4-18
For reference only
Honeywell • Sensing and Control
3
Model Z
High Range Wet/Wet Differential Pressure Transducer
RANGE CODES
Range Code
Available ranges
DL
±2000 psid
DN
±3000 psid
DR
±5000 psid
DT
±7500 psid
DV
±10000 psid
Warranty. Honeywell warrants goods of its manufacture as
being free of defective materials and faulty workmanship.
Honeywell’s standard product warranty applies unless agreed
to otherwise by Honeywell in writing; please refer to your
order acknowledgement or consult your local sales office for
specific warranty details. If warranted goods are returned to
Honeywell during the period of coverage, Honeywell will repair
or replace, at its option, without charge those items it finds
defective. The foregoing is buyer’s sole remedy and is in lieu
of all warranties, expressed or implied, including those of
merchantability and fitness for a particular purpose. In no
event shall Honeywell be liable for consequential, special, or
indirect damages.
WIRING CODES
Connector
Unamplified
A, B
(+) excitation
C, D
(-) excitation
E
(-) output
F
(+) output
While we provide application assistance personally, through our
literature and the Honeywell web site, it is up to the customer to
determine the suitability of the product in the application.
NOTES
1. Availability varies according to range.
2. Interconnecting shunt cal. 1 terminal with shunt cal. 2 terminal provides 50% (unamplified units), 75% (4 mA to 20 mA 3-wire units) or
80% (voltage amplified units of full scale output for quick calibration.
Shunt calibration comes standard with internal amplifier options 2b,
2c, 2t and 2j.
3. O=Orange, Y=Yellow, B=Blue, Bl=Black, R=Red, Br=Brown,
W=White, G=Green. Color specifying cable and number or letter
specifying connector.
4. No mating connector necessary for cable option.
5. Some pressure port options may require axial orientation.
6. Only available with unamplified option 2u.
7. Only available with amplified options.
8. Only available with Vdc output options 2b, 2c.
9. Consult factory for TEDS availability with amplified models.
10. Range dependent; consult factory. Termination dependent; consult
factory.
11.Internal amp and termination dependent; consult factory.
12.5000 ohm bridge required.
Note: Unless otherwise specified on order, amplified units with 4 mA
to 20 mA output will provide 4 mA at 0 psid and 20 mA at positive full
scale and the unit will not operate in the negative direction. An available alternative is to specify 4 mA at negative full scale and 20 mA at
positive full scale. All amps add 2 in to amplifier housing.
Specifications may change without notice. The information we
supply is believed to be accurate and reliable as of this printing.
However, we assume no responsibility for its use.
For more information about Sensing and Control products, visit
www.honeywell.com/sensing or call +1-815-235-6847
Email inquiries to [email protected]
WARNING
PERSONAL INJURY
•DO NOT USE these products as safety or emergency
stop devices or in any other application where failure of
the product could result in personal injury.
Failure to comply with these instructions could result in
death or serious injury.
WARNING
MISUSE OF DOCUMENTATION
•The information presented in this catalogue is for
reference only. DO NOT USE this document as product
installation information.
•Complete installation, operation and maintenance
information is provided in the instructions supplied with
each product.
Failure to comply with these instructions could result in
death or serious injury.