PD-Series - Carling Technologies

PD-Series
Ground Fault Circuit Protection
SmartGuard is an equipment ground fault protection device
that functions as a standard high-quality Carling hydraulic/
magnetic circuit breaker, offering customized overload and
short circuit protection. In addition, this breaker senses
and guards against faults to ground using a state of the art
integrated circuit developed by Carling. This new technology
detects faults and when a fault occurs, the breaker trips and
an LED illuminates. The LED gives a clear indication that the
trip occurred as a result of leakage. This protection helps
prevent serious equipment damage and fire.
Features:
ŠŠ Overload, short circuit and ground fault protection in a single package
ŠŠ Handle style actuators with optional “handleguard”
ŠŠ Wiping Contacts - Mechanical linkage with two-step actuation – cleans contacts, provides high, positive contact pressure & longer contact life
ŠŠ A trip-free mechanism, a safety feature, makes it impossible to manually hold the contacts closed during overload or fault conditions.
ŠŠ A common trip linkage between all poles, another safety feature, ensures that an overload in one pole will trip all adjacent poles.
ŠŠ Front panel or DIN rail mounting options
ŠŠ “State of the art” integrated circuit developed by Carling
ŠŠ Equipment leakage sensitivity from 10 to 100 milliamps
ŠŠ Integral push-to-test button and LED “tripped” indicator
ŠŠ Immediate reset after fault has been cleared
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062-1177
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: [email protected] • www.carlingtech.com
Agency Certifications:
UL Standard 1077
UL Standard 943
CSA Certified
TUV Certified
Component Recognition Program as
Equipment Leakage Circuit Interrupter
and, Protectors, Supplementary (FTTJ2, File
E177510).
Tested as Ground Fault Circuit Interrupters
for Equipment Protection.
Component Equipment Leakage Current
Interrupter with Supplementary Protector,
under Class C22.2,No. 144-M91, FIle
LR47848-50
IEC 947-2 and appendix B: Circuit Breakers
incorporating Residual Current Protection.
Complies with waveform requirements of
IEC 1008-1, Type A.
2 | PD-Series Circuit Breaker - General Specifications
Electrical Tables
Table A: Lists UL Recognized & CSA Certified configurations and
performance capabilities as a Component Supplementary Protector.
Table B: Lists TUV Certified configurations and performance capabilities
as a Circuit breaker incorporating residual current protection.
PD-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTOR & EARTH LEAKAGE CURRENT INTERRUPTER
VOLTAGE
CIRCUIT
CURRENT RATING
INTERRUPTING
LEAKAGE
CAPACITY (AMPS)
CURRENT
FULL
GENERAL
MAX RATING
FREQUENCY
LOAD
PURPOSE
WITHOUT
RATING
VOLTS
HERTZ
PHASE
AMPS
AMPS
BACKUP FUSE
(MILLIAMPS)
120/208
50/60
1
1-50
---
5000
7-100
120/208
50/60
31
1-50
---
5000
7-100
CONFIGURATION
SERIES
UL / CSA
MUST - TRIP
208-240
50/60
3
1-50
---
2000
7-100
480Y
50/60
3
1-30
30.1-50
2000
7-100
Electrical
Maximum Voltage AC, 480 WYE/277 VAC, 50/60 Hz
Standard Current Ratings 1.00, 2.50, 5.00, 7.50, 10.0, 15.0,
20.0, 25.0, 30.0, 35.0, 40.0 & 50.0
amps. For other ratings, consult factory.
Insulation Resistance
Minimum of 100 Megohms @ 500 VDC.
Dielectric Strength
1960 VAC, 60 Hz for one minute
between all electrically isolated
terminals.
Resistance, Impedance from Line to Load Terminal
(Values Based on Series Trip Circuit
Breaker)
RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
Mechanical
Endurance
Trip Free
Trip Indication
Ampere Rating
10,000 ON-OFF operations @ 6 per
minute; with rated current and voltage.
All SmartGuard equipment leakeage
circuit breakers will trip on overload
or leakage to ground, even when
actuator is forcibly held in the ON
position.
The actuator moves to the OFF
position when an overload or earth
leakage ground fault causes the
breaker to trip. The LED is illuminated
when leakage to ground causes the
circuit breaker to trip.
Physical
20.1 - 50.0
Pulse Tolerance Curve
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
Multiple of
Rated Current
Ir
Time Delay Curves
22, 24, 26
12x
t
4.165
8.33
16.67
Time in
Milliseconds
Leakage To Ground
Standard Must Trip
Leakage Current Ratings
Trip Time
Test Button
Leakage Trip Indicator
7, 10, 15, 30, 50 & 100 milliamps. For
other ratings, consult factory.
300 ms Max. @ 100%, 40ms Max. @
500% of must trip leakage current.
On breaker face above actuator.
Red LED on breaker face above
actuator.
Number of Poles
2, 3 & 4
Length (included switched
or unswitched neutral)
4.2 inches ( 106.7 mm)
Width
2-pole: 3.0 inches (76.2 mm)
3-pole: 3.75 inches (95.3 mm)
4-pole: 4.5 inches (114.3 mm)
Depth
2.5inches (63.5mm).
Weight: 2-pole
16.0 oz. (453.6 gm)
3-pole: 21.4 oz. (606.7 gm)
4-pole: 26.9 oz. (762.6 gm)
Standard Colors
Housing - gray;
Actuator - black, red, or white
Mounting
Front Panel or Standard 35mm
Symmetrical DIN Rail (35 x 7.5 or
35 x 15mm per DIN EN5002).
Termination
Box Lug
Environmental
Operating Temperature +10°C to +50°C
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PD-Series – Circuit & Terminal Diagrams | 3
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
Notes:
Other time delay values available, consult factory.
Delay Curves 21,22,24,26: Breakers to hold 100% and must trip at 125%
of rated current and greater within the time limit shown in this curve.
Delay Curve 20: Breakers to hold 100% and must trip at 150% of rated
current and greater within the time limit shown in this curve.
All Curves: Curve data shown represents breaker response at ambient
temperature of 77°F (25°C) with no preloading. Breakers are mounted in
standard wall-mount position.
The minimum inrush pulse tolerance handling capability is 12 times the
rated current. These values are based on a 60 Hz 1/2 cycle, 8.33 ms pulse.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
4 | PD-Series – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PC-Series – Ordering Scheme | 5
PD R – B – 24 – 650 – B – 2 A 1 – 1 – C
1
Series
3
Circuit
2
System
Voltage/Poles
4
Frequency
& Delay
5
Current Rating
1 SERIES
PD
Poles
One plus unswitched neutral
Two
Two plus unswitched neutral
Two plus switched neutral
Three
Three plus unswitched neutral
Three plus switched neutral
Three
Three plus unswitched neutral
Three plus switched neutral
3 CIRCUIT
Series Trip (Current)
4 FREQUENCY & DELAY
20
22
410
512
415
517
420
522
425
527
430
435
440
24
26
50/60Hz Instantaneous
50/60Hz Short
AMPERES
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
3.000
3.500
4.000
8
Actuator
9
Actuator
Color
10
Mounting
11
Agency
Approval
445
450
455
460
465
470
475
480
485
490
495
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
7 TERMINAL
2
Front Connected Box Lug
8 ACTUATOR
A
Handle
B
Handle w/ handleguard
9 ACTUATOR COLOR & LEGEND4
Acuator Color
I-O
ON-OFF
White
A
B
Black
C
D
Red
E
F
Legend Color
Black
White
White
Dual
1
2
3
10 MOUNTING3
1 THREADED INSERT 6-32 X 0.195 INCHES
2 THREADED INSERT ISO M3 X 6.5 MM
50/60Hz Medium
50/60Hz Long
11 AGENCY APPROVAL
UL Recognized & CSA Certified
C
TUV Certified
U
5 CURRENT RATING (AMPERES)
CODE
7
Terminal
6 EQUIPMENT LEAKAGE - TRIP CURRENT (MILLIAMPS)2
B
7
D
15
F
50
C
10
E
30
G
100
2 SYSTEM VOLTAGE / POLES1
System Voltage
120VAC 1Ø
A
120/240 VAC 1Ø
B
120/208 VAC 1Ø,
C
120/240 VAC 1Ø
120/208 VAC 1Ø,
D
120/240 VAC 1Ø
208/240 VAC 3Ø
E
208/240 VAC 3Ø
F
208/240 VAC 3Ø
G
480Y VAC 3Ø
P
480Y VAC 3Ø
Q
480Y VAC 3Ø
R
B
6
Equipment
Leakage Trip Current
610
710
611
711
612
712
613
614
615
616
617
10.000
10.500
11.000
11.500
12.000
12.500
13.000
14.000
15.000
16.000
17.000
Time Delay Curves
618
620
622
624
625
630
635
640
650
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
50.000
Notes:
1 Units with a switched or unswitched neutral connection are the same size as a unit with an additional breaker pole (e.g. a 2-pole unit with a switched or unswitched neutral is the same physical size as a 3-pole unit.)
Switched neutral poles contain the same overcurrent protection as the other poles.
2 The leakage currents shown will cause the breaker to trip (must-trip current). The must-
hold current is 67% of the must-trip current.
3 All breakers are front panel mountable using screw size shown. Breakers may also be mounted on either 35mm x 7.5mm or 35mm x 15mm symmetrical DIN rail.
4 TUV certifed units must have I-O or Dual legends
Instantaneous
Medium
Short
Long
REV_GFCI_PD_0312
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231