E-Series Circuit Breaker Datasheet [pdf]

E-Series
E-Series
CIRCUIT BREAKER
The E-Series hydraulic-magnetic circuit breaker is ideally suited for higher current and voltage applications. It is
UL listed and CSA certified for branch circuit protection, which does not require a fuse back up. It is also UL
recognized and CSA certified as a supplementary protector and as a manual motor controller.
Its physical features include front and back mounting, screw and stud terminals and heavy duty box wire
connectors for solid wire or a pressure plate connector for standard wire. The E-series is available with handle
actuators and can be configured as .1-125 amps, up to 600VAC or 125VDC, with choice of time delays, actuator
colors and 1 to 6 poles configuration. Additionally, a Power Selector device is also available.
Product Highlights:
UL listed and CSA certified
Certified for circuit branch protection
ŠŠ Recognized as a supplementary protector
and as a manual motor controller
ŠŠ Optional power selector device
ŠŠ
ŠŠ
Typical Applications:
High Voltage/High
Current Applications
ŠŠ Renewable Energy
ŠŠ Military
ŠŠ Industrial Controls
ŠŠ Generators
ŠŠ
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: [email protected]
Application Support: [email protected]
Phone: 860.793.9281 Fax: 860.793.9231
www.carlingtech.com
2 | E-Series Circuit Breaker - General Specifications
Electrical
Maximum Voltage
600VAC 50/60 Hz, 125VDC (See Table A)
Current Ratings
Standard current coils: 0.100, 0.250, 0.500, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 50.0, 60.0, 70.0 & 100 Amp.
Auxiliary Switch Rating SPDT; 10.1A 250VAC, 1.0A 65VDC; 0.5A 80VDC, 0.1A 125VAC
(with gold contacts).
Insulation Resistance
Minimum of 100 Megohms at 500 VDC.
Dielectric Strength
UL, CSA: 2200 V 50/60 Hz for one minute between all electrically isolated terminals. E-Series Circuit Breakers comply with the 8mm spacing and 3750V 50/60 Hz dielectric requirements from hazardous voltage to operator accessible surfaces, between adjacent poles and from main circuits to auxiliary circuits per Publications EN 60950 and VDE 0805.
Resistance, Impedance Values from Line to Load Terminal - based on Series Trip Circuit Breaker.
CURRENT
TOLERANCE
(AMPS)
(%)
0.10 - 5.0
5.1 - 20.0
± 15
± 25
20.1 - 50.0
± 35
Mechanical
Endurance
10,000 ON-OFF operations @ 6 per minute; with rated Current and Voltage.
Trip Free
All E-Series Circuit Breakers will trip on overload, even when Handle is forcibly held in the ON position.
Trip Indication
The operating Handle moves positively to the OFF position when an overload causes the breaker to trip.
Physical
Number of Poles
Mounting
Connectors, Box Type
Internal Circuit Configuration
Weight
Standard Colors
1-6
A 3” minimum spacing must be
provided between the circuit breaker arc venting area on back
connected E-Series circuit breakers and grounded obstructions. E-Series circuit breakers must be mounted on a vertical surface.
Front connected E-Series circuit breakers are supplied with box type pressure connectors that accept copper or aluminum conductors as follows: 1/0-14 Copper, 1/0-12 Aluminum.
Series and Switch Only, (with or
without auxiliary switch). Shunt with current coils.
Approximately 252 grams/pole (Approximately 9 ounces/pole)
Housing-Black; Actuator - See Ordering Scheme.
Environmental
Designed in accordance with requirements of specification
MIL PRF-55629 & MIL-STD-202G as follows:
Pulse Tolerance Curves
Time Delay Curves
62, 64 & 66
(100 Amps Max.)
Time Delay Curves
22, 24 & 26 (100 Amps Max.)
Shock
Withstands 100 Gs, 6ms, sawtooth while carrying rated current per Method 213, Test Condition “I”.
Vibration
Withstands 0.060” excursion from 10-55 Hz, and 10 Gs 55-500 Hz, at
rated current per Method 204C, Test Condition A.
Moisture Resistance
Method 106D, i.e., ten 24-hour cycles @ + 25°C to +65°C, 80-98% RH.
Salt Spray
Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock
Method 107D, Condition A (Five cycles @ -55°C to +25°C to +85°C to +25°C).
Operating Temperature -40° C to +85° C
*Manufacturer reserves the right to change product specification without prior notice.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
E-Series Circuit Breaker - General Specifications | 3
Electrical Tables
Table A: Lists UL Listed (489) & CSA Certified (C22.2 No. 5) configurations & performance capabilities as a Molded Case
Circuit Breaker.
E SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS
VOLTAGE
CIRCUIT
CONFIGURATION
SERIES
CURRENT RATING
MAX.
RATING
FREQUENCY
PHASE
FULL LOAD AMPS
INTERRUPTING
CAPACITY (AMPS)
HIGH
INTERRUPTING
CAPACITY
WITHOUT BACKUP
(AMPS)
FUSE
80
DC
---
0.10 - 100
5,000
50,000
125
DC
---
0.10 - 100
5,000
10,000
125
DC
---
0.10 - 125
10,000
---
120
50 / 60
1
0.10 - 125
10,000
---
240
240
50 / 60
50 / 60
1
1
0.10 - 30
31 - 100
5,000
5,000
10,000
120 / 240
50 / 60
1
0.10 - 30
5,000
10,000
120 / 240
50 / 60
1
31 - 100
5,000
---
120 / 240
50 / 60
1
101 - 125
10,000
---
240
50 / 60
3
0.10 - 100
5,000
---
Table B: Lists UL Recognized & CSA Accepted configurations & performance capabilities as a Component Supplementary
Protector.
E -SERIES TABLE B: COMPONENT SUPPLEMENTARY PROTECTORS
CURRENT RATING
SHORT CIRCUIT CAPACITY (AMPS)
UL/CSA
FULL LOAD
GENERAL
FREQUENCY
PHASE
WITH
BACKUP
WITHOUT
AMPS
PURPOSE AMPS
FUSE3
BACKUP FUSE
VOLTAGE
CIRCUIT
CONFIGURATION
MAX.
RATING
APPLICATION CODES
UL
CSA
125
DC
---
0.02 - 100
---
---
5,000
TC1,2, OL1, U1 TC1,2, OL1, U1
125
150
DC
DC
-----
-----
101 - 120
0.02 - 125
-----
5,000
5,000
TC1,2, OL0, U1 TC1,2, OL0, U1
TC1, OL0, U3 TC1, OL0, U3
160
150 / 300
DC
DC
-----
0.02 - 100
0.02 - 100
-----
-----
5,000
5,000
TC1,2, OL1, U1 TC1,2, OL1, U1
TC1,2, OL1, U1 TC1,2, OL1, U1
SERIES &
120 / 240
50 / 60
1
---
0.02 - 100
---
5,000
TC1,2, OL0, U1 TC1,2, OL0, U1
SHUNT
240
250
50 / 60
50 / 60
1
1
0.02 - 100
0.02 - 100
-----
--10,000
5,000
---
TC1,2, OL1, U1 TC1,2, OL1, U1
TC1,2, OL1, C1 TC1,2, OL1, C1
277
50 / 60
1
0.02 - 100
---
--10,000
5,000
---
TC1,2, OL1, U1 TC1,2, OL1, U1
TC1,2, OL1, C1 TC1,2, OL1, C1
480
50 / 60
50 / 60
50 / 60
1&3
1&3
1&3
0.02 - 100
0.02 - 50
0.02 - 100
-------
10,000
10,000
10,000
-------
TC1,2, OL1, C1 TC1,2, OL1, C1
TC1,2, OL1, C1 TC1,2, OL1, C1
TC1,2, OL1, C1 TC1,2, OL1, C1
DC
---
---
0.02 - 125
---
5,000
DC
---
0.02 - 120
160
DC
---
0.02 - 100
240
277
50 / 60
50 / 60
1
1
0.02 - 100
0.02 - 100
480
600
50 / 60
50 / 60
1&3
1&3
0.02 - 100
0.02 - 100
480 1
600
600 2
125
SWITCH
ONLY
TC1, OL0, U3
Notes:
1 Per pole opposite polarity rating - Delta Configuration.
2 4 Poles connected in series
3 Requires branch circuit backup with a UL Listed Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amp rating and not to exceed 225A.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
TC1, OL0, U3
4 | E-Series Circuit Breaker - General Specifications
Electrical Tables
Table C: Lists UL Recognized, CSA Accepted and VDE Certified configurations and performance capabilities as a
Component Supplementary Protector.
E -SERIES TABLE C: COMPONENT SUPPLEMENTARY PROTECTORS WITH VDE
CURRENT RATING
VOLTAGE
CIRCUIT
CONFIGURATION
SHORT CIRCUIT CAPACITY (AMPS)
UL/CSA
MAX.
FREQUENCY PHASE FULL LOAD AMPS WITH BACKUP
RATING
FUSE1
125
DC
---
0.1 - 100
---
WITHOUT
BACKUP
FUSE
WITHOUT
BACKUP
FUSE
5,000
5,000
SERIES &
240
50 / 60
1&3
0.1 - 100
---
5,000
5,000
SHUNT
415
50 / 60
1&3
0.1 - 100
10,000
---
4,000
SWITCH ONLY
125
DC
---
0.1 - 125
240
50 / 60
1&3
0.1 - 100
415
50 / 60
1&3
0.1 - 100
APPLICATION CODES
VDE (Icn)
UL
CONSTRUCTION NOTES
CSA
TC1,2, OL1, U1 TC1,2, OL1, U1
1 or 2 Poles
1 - 5 Poles. Up to 4
TC1,2, OL1, U1 TC1,2, OL1, U1 Current Poles, 1 Voltage
Pole
2 - 5 Poles. Up to 4
TC1,2, OL1, C1 TC1,2, OL1, C1 Current Poles, 1 Voltage
Pole
Notes:
1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amp rating and not to exceed 225 amps.
Table D: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
E SERIES TABLE D : UL1500 (Marine Ignition Protection)
VOLTAGE
CIRCUIT
CONFIGURATION
SERIES
MAX.
RATING
FREQUENCY
CURRENT RATING
SHORT CIRCUIT
CAPACITY (AMPS)
FULL LOAD AMPS
WITHOUT BACKUP
FUSE
UL
CSA
PHASE
65
DC
---
0.02 - 100
5,000
TC1,2,OL1,U1
TC1,2,OL1,U1
125
50 / 60
1
0.02 - 100
1,500
TC1,2,OL1,U1
TC1,2,OL1,U1
250
50 / 60
1
0.02 - 100
1,500
TC1,2,OL1,U1
TC1,2,OL1,U1
Agency Certifications
UL Recognized
UL Standard 1077
UL Standard 1500
UL Listed
UL Standard 489
APPLICATION CODES
Component Recognition Program
as Protectors, Supplementary
(Guide QVNU2, File E75596)
CSA Accepted
Component Supplementary
Protector (Class 3215 30, File
047848 0 000)
CSA Standard C22.2 No. 235
Component Recognition Program
as Manual Motor Controls (Guide
NLRV2, File E135367)
CSA Certified
Circuit Breaker Molded Case
(Class 1432 01, File 093910),
CSA Standard C22.2 No. 5.1 - M
Protectors, Supplementary for
Marine Electrical & Fuel Systems
(Guide PEQZ2, File E75596)
Ignition Protection
TUV Certified
EN60934 under License No.
R72031056
VDE Certified
EN60934, VDE 0642 under File
No. 10537
Circuit Breakers, Molded Case
(Guide DIVQ, File E129899)
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
E-Series Circuit Breaker - Handle UL Recognized – Ordering Scheme | 5
E A 2
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
5
Auxiliary
Switch
24
450
6
Frequency
& Delay
7
Current Rating
2 ACTUATOR
A
Handle, one per pole
3Three
4Four
4 CIRCUIT 2
A 3 Switch Only (no coil)
B
Series Trip (current)
C
Series Trip (voltage)
D
Shunt Trip (current)
6 FREQUENCY & DELAY
03 3 DC 50/60Hz, Switch Only 10 5 DC Instantaneous
12 DC Short
14 DC Medium
16 DC Long
20 5 50/60Hz Instantaneous
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
32 DC, 50/60Hz Short
E
F
G
Shunt Trip (voltage)
Relay Trip (current)
Relay Trip (voltage)
S.P.S.T. 0.110 Q.C. Terminals
S.P.S.T. 0.110 Q.C. Terminals
(Gold Contacts)
S.P.S.T. 0.187 Q.C. Terminals
S.P.D.T. 0.187 Q.C. Terminals
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
62 50/60Hz Short, Hi-Inrush
64 50/60Hz Medium, Hi-Inrush
66 50/60Hz Long, Hi-Inrush
72 DC, Short,Hi-Inrush
74 DC,Medium, Hi-Inrush
76 DC, Long, Hi-Inrush
92 6DC, 50/60Hz Short, Hi-Inrush
94 6DC, 50/60Hz Medium, Hi-Inrush
96 6DC, 50/60Hz Long, Hi-Inrush
11
Maximum
Application
Rating
0.350
0.400
0.450
0.500
0.550
0.600
0.650
0.700
0.750
0.800
0.850
0.900
0.950
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
430
435
440
445
450
455
460
465
470
475
480
485
490
495
610
710
611
711
612
712
613
3.000
3.500
4.000
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
10.000
10.500
11.000
11.500
12.000
12.500
13.000
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS) 5
A06 6 DC, 5 DC
A65 65 DC, 55 DC
J48
A12 12 DC, 10 DC
B25 125 DC, 100 DC J65
A18 18 DC, 15 DC
J06 6 AC, 5 AC
K20
A24 24 DC, 20 DC
J12 12 AC, 10 AC
L40
A32 32 DC, 25 DC
J18 18 AC, 15 AC
A48 48 DC, 40 DC
J24 24 AC, 20 AC
614
615
616
617
618
620
622
624
625
630
635
640
650
660
670
680
690
810
811
812
912 8
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
50.000
60.000
70.000
80.000
90.000
100.000
110.000
120.000
125.000
48 AC, 40 AC
65 AC, 55 AC
120 AC, 65 AC
240 AC, 130 AC
Notes:
1 VDE approval on 1-5 poles only. Standard multi-pole units identical poles except when specifying auxiliary switch - (see Note 4). For mixed ratings, consult factory.
2 Switch Only & Series Trip construction available with either front or back connected
terminals.
Shunt construction available with back connected terminals, (Terminal Codes 1 & 2) only. Circuit Codes B,C & D are VDE approved.
3 Switch Only construction: 30 amps or less select Current Rating Code 630; 31-70 amps, select Current Rating code 670; 71-100 amps, select Current Rating Code 810; 101-125 amps Select Current Rating Code 912. Switch Only is VDE approved only if tied to a protected pole.
12
Agency
Approval
MAX. RATING
50 A
120 A
50 A
100 A
Dual
Legend Color
1Black
2White
3White
4White
5White
6Black
7Black
8Black
10 MOUNTING / BARRIERS
BACK CONNECTED (FRONT MOUNTED ONLY)
Mounting Inserts
A6-32
B ISO M3
CODEAMPERES
235
240
245
250
255
260
265
270
275
280
285
290
295
410
512
415
517
420
522
425
527
10
Mounting/
Barriers
9 ACTUATOR COLOR & LEGEND 13
Actuator Color
I-O
ON-OFF
White
AB
Black
CD
Red
FG
Green
HJ
Blue
KL
Yellow
MN
Gray
PQ
Orange
RS
7 CURRENT RATING (AMPERES) 7
0.020
0.025
0.030
0.035
0.040
0.045
0.050
0.055
0.060
0.065
0.070
0.075
0.080
0.085
0.090
0.095
0.100
0.150
0.200
0.250
0.300
9
Actuator
Color
FRONT CONNECTED (BACK MOUNTED ONLY)
MAX. RATING
3 10 Box Wire Connector (Line & Load)
100 A
11
C Box Wire Connector with Pressure Plate (Line & Load)
100 A
4
10-32 Screw (Line & Load)
50 A
D
M5 Screw (Line & Load)
50 A
5
10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load)
50 A
E
M5 “Bus-Type” Screw (Line), 10-32 Screw (Load)
50 A
6 10 10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
F 11 10-32 “Bus-Type” Screw (Line), Box Wire Connector
with Pressure Plate (Load)
100 A
7
1/4-20 Screw (Line & Load)
100 A
G
M6 Screw (Line & Load)
100 A
8
1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load)
100 A
H
M6 “Bus-Type” Screw (Line), M6 Screw (Load)
100 A
10
9 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
J 11 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector
with Pressure Plate (Load)
100 A
5Five
6Six
5 AUXILIARY SWITCH 4
0 without Auxiliary Switch
6
2 S.P.D.T. 0.110 Q.C. Terminals
7
3 S.P.D.T. 0.139 Solder Lug
4 S.P.D.T. 0.110 Q.C. Terminals
8
(Gold Contacts)
9
020
025
030
035
040
045
050
055
060
065
070
075
080
085
090
090
210
215
220
225
230
8
Terminal
C B
8 TERMINAL 12
BACK CONNECTED (FRONT MOUNTED ONLY)
1 9 10-32 Stud (All Terminals)
2 9 1/4-20 Stud (All Terminals)
A 9 M5 Stud (Line & Load)
B 9 M6 Stud (Line & Load)
1 SERIES
E
3 POLES 1
1
One
2Two
1 2 A
FRONT CONNECTED (BACK MOUNTED ONLY) 14
Back Mounting Foot Type Front Mounting Inserts (Optional Use)
CShort
6-32
D Short
ISO M3
ELong
6-32
F
Long
ISO M3
11 MAXIMUM APPLICATION RATING 15
A
65 VDC, 120 A G 16
B
125 VDC, 120 A
H 16
C
120/240 VAC, 100 A
J 16
D
240 VAC, 100 A
L 16
E 16 277/480 VAC, 100 A
T
F
277 VAC, 100 A
W 16
600 VAC, 100 A
480 VAC, 100 A
415 VAC, 100 A
160 VDC, 100 A
125 VDC/240 VAC, 100 A
125 VDC/415 VAC, 100 A
12 AGENCY APPROVAL
B UL 1077 / UL508 Recognized & CSA Accepted
D UL 1077 Recognized, CSA Accepted, & VDE Certified
4
5
6
7
8
9
10
11
12
13
14
15
16
Auxiliary Switch available on Switch Only and Series Trip units. On multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme right pole. Back mounted units require special mounting provisions when auxiliary switch is specified. VDE approval on Auxilary Switch Codes 0,2,3 & 4 only.
Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay Codes 10 & 20. Series Trip construction with a voltage coil s VDE approved only if tied to a protected pole.
Frequency & Delay Codes 92,94 & 96 are not VDE Certified.
Current Coil Ratings 0.100 - 100 ams are VDE Certified.
125 A rating (Code 912) available as a Switch Only (Circuit Code A), rated 125 VDC (Code B).
An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 (Terminal Code 1). 1/4-20 (Code 2), M5 (Code A), and M6 (Code B) terminals per UL requirement.
Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG. aluminum wire.
Box Wire Connector with Pressure Plate for stranded wire, consult factory for details.
Terminal Codes A,B,D,E,G & H are not VDE Certified.
VDE approvals require Dual (I-O, ON-OFF) or I-O markings on all handles.
Back Mounted breakers can also be front mounted by utilizing the proper front panel mounting inserts normally supplied. However, terminal connections must be made prior to mounting.
Application ratings B,D,J,T & W are available with VDE.
415, 480 & 600 VAC ratings require 3 or 4 pole break 3Ø and 2 pole break 1Ø.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
6 | E-Series Circuit Breaker - Handle UL Listed – Ordering Scheme
E A 2
1
Series
2
Actuator
24
450
6
Frequency
& Delay
7
Current Rating
B 0
4
Circuit
3
Poles
5
Auxiliary
Switch
2 ACTUATOR
A
Handle, one per pole
3 POLES 1
1
One
2Two
3Three
4Four
5Five
6Six
4 CIRCUIT 2
B
Series Trip (current)
C 3 Series Trip (voltage)
5 AUXILIARY SWITCH 4
0 without Auxiliary Switch
6
2 S.P.D.T. 0.110 Q.C. Terminals
7
3 S.P.D.T. 0.139 Solder Lug
4 S.P.D.T. 0.110 Q.C. Terminals
8
(Gold Contacts)
9
S.P.S.T. 0.110 Q.C. Terminals
S.P.S.T. 0.110 Q.C. Terminals
(Gold Contacts)
S.P.S.T. 0.187 Q.C. Terminals
S.P.D.T. 0.187 Q.C. Terminals
6 FREQUENCY & DELAY
10 5 DC Instantaneous
62 50/60Hz Short, Hi-Inrush
12 DC Short
64 50/60Hz Medium, Hi-Inrush
14 DC Medium
66 50/60Hz Long, Hi-Inrush
16 DC Long
72 DC, Short,Hi-Inrush
20 5 50/60Hz Instantaneous
74 DC,Medium, Hi-Inrush
22 50/60Hz Short
76 DC, Long, Hi-Inrush
24 50/60Hz Medium
26 50/60Hz Long
7 CURRENT RATING (AMPERES) 7
CODEAMPERES
0.020
0.025
0.030
0.035
0.040
0.045
0.050
0.055
0.060
0.065
0.070
0.075
0.080
0.085
0.090
0.095
0.100
0.150
0.200
0.250
0.300
9
Actuator
Color
10
Mounting/
Barriers
8 TERMINAL 7
BACK CONNECTED (FRONT MOUNTED ONLY)
1 8 10-32 Stud (All Terminals)
2 8 1/4-20 Stud (All Terminals)
1 SERIES
E
020
025
030
035
040
045
050
055
060
065
070
075
080
085
090
090
210
215
220
225
230
1 2 A
8
Terminal
235
240
245
250
255
260
265
270
275
280
285
290
295
410
512
415
517
420
522
425
527
0.350
0.400
0.450
0.500
0.550
0.600
0.650
0.700
0.750
0.800
0.850
0.900
0.950
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
430
435
440
445
450
455
460
465
470
475
480
485
490
495
610
710
611
711
612
712
613
3.000
3.500
4.000
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
10.000
10.500
11.000
11.500
12.000
12.500
13.000
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS) 5
A06 6 DC, 5 DC
A65 65 DC, 55 DC
J48
A12 12 DC, 10 DC
B25 125 DC, 100 DC J65
A18 18 DC, 15 DC
J06 6 AC, 5 AC
K20
A24 24 DC, 20 DC
J12 12 AC, 10 AC
L40
A32 32 DC, 25 DC
J18 18 AC, 15 AC
A48 48 DC, 40 DC
J24 24 AC, 20 AC
614
615
616
617
618
620
622
624
625
630
635
640
650
660
670
680
690
810
811
812
912 8
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
50.000
60.000
70.000
80.000
90.000
100.000
110.000
120.000
125.000
48 AC, 40 AC
65 AC, 55 AC
120 AC, 65 AC
240 AC, 130 AC
C C
11
Maximum
Application
Rating
12
Agency
Approval
MAX. RATING
50 A
125 A
FRONT CONNECTED (BACK MOUNTED ONLY)
MAX. RATING
3 9 Box Wire Connector (Line & Load)
100 A
C 10 Box Wire Connector with Pressure Plate (Line & Load)
100 A
4
10-32 Screw (Line & Load)
50 A
5
10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load)
50 A
6 9 10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
F 10 10-32 “Bus-Type” Screw (Line), Box Wire Connector
with Pressure Plate (Load)
100 A
7
1/4-20 Screw (Line & Load)
125 A
8
1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load)
100 A
9 9 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
J 10 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector
with Pressure Plate (Load)
100 A
9 ACTUATOR COLOR & LEGEND 12
Actuator Color
ON-OFF Dual
Legend Color
White
B1Black
Black
D2White
Red
G3White
Green
J4White
Blue
L5White
Yellow
N6Black
Gray
Q7Black
Orange
S8Black
10 MOUNTING / BARRIERS
BACK CONNECTED (FRONT MOUNTED ONLY)
Mounting Inserts
A6-32
B ISO M3
FRONT CONNECTED (BACK MOUNTED ONLY) 11
Back Mounting Foot Type Front Mounting Inserts (Optional Use)
CShort
6-32
D Short
ISO M3
ELong
6-32
F
Long
ISO M3
11 MAXIMUM APPLICATION RATING 15
1
120 VAC
B
125 VDC, 120 A
13
C 120/240 VAC, 100 A
D
240 VAC, 100 A
12 AGENCY APPROVAL
C UL 489 Listed & CSA Certified
F UL 489 Listed, CSA Certified, & VDE Certified
Notes:
1 Standard multi-pole units identical poles except when specifying auxiliary switch (see Note 4). For mixed ratings, consult factory. VDE Certification on 1-5 poles only.
2 Series Trip construction available with either front or back connected terminals. 3 Series Trip construction with a voltage coil is not available as a single pole unit and must be tied to a protected pole.
4 On multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme right pole per Figure A. Back mounted units require special mounting provisions when
auxiliary switch is specified. VDE Certification on auxilary switch codes 0, 2, 3 & 4 only.
5 Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay Codes 10 & 20.
6 Frequency & Delay Codes 92, 94 & 96 are not VDE Certified.
7 Current Ratings under 0.100 amps are not VDE Certified .
8 An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 Stud (Terminal Code 1) or 1/4-20 Stud (Code 2) terminals per UL requirement.
9 Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG. aluminum wire.
10 Box Wire Connector with Pressure Plate for stranded wire, consult factory for details.
11 Back Mounted breakers can also be front mounted by utilizing the proper front panel mounting inserts normally supplied. However, terminal connections must be made prior to mounting.
12 VDE Certification requires dual (I-O , ON-OFF) markings on all handles.
13 Not available with VDE Certification.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
E-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams | 7
Circuit & Terminal Diagrams: in. [mm]
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
3 0-50 amps: 10-32 & M5 Studs .625±.062/15.88±1.574 long.
4 51-120 amps: 1/4-20 & M6 Studs .750±.062/19.05±1.574 long.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
8 | E-Series Circuit Breaker - Handle (Back Connected) – Dimensional Specifications
Dimensional Specifications: in. [mm]
Notes:
1 1/4 -20 stud terminal in Series Trip circuit configuration shown.
2 A 3” min spacing must be provided between the circuit breaker arc venting area of back connected E-Series circuit breaker and grounded obstructions.
3 All dimensions are in inches [millimeters].
4 Tolerance ±.020 [.51] unless otherwise specified.
5 Circuit breakers must be mounted on vertical surface.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
E-Series Circuit Breaker - Handle (Front Connected) – Dimensional Specifications | 9
Dimensional Specifications: in. [mm]
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
3 Box wire connector terminal in Series Trip circuit configuration shown.
4 Circuit breakers must be mounted on vertical surface.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
10 | E-Series Circuit Breaker - Time Delay Values
NOTES
Delay Curves 10,20,30: Breakers to hold 100% and must trip at 150% of rated current and greater wthin the time limit shown in these curves.
Delay Curves 12,14,16,22,24,26,62,64,66,72,74,76: Breakers to hold 100% and must trip at 125% of rated current and greater wthin the time limit shown in these curves.
Delay Curves 32,34,36,92,94,96: Breakers to hold 100% and must trip at 135% of rated current and greater wthin the time limit shown in these curves.
All curves: Data shown represents breaker response at ambient temperature of 77°F (25°C) with no preloading: Breakers are mounted in standard wall-mount position.
The minimum inrush pulse tolerance handling capacity on the above standard delays is 16 times rated current &20 times rated current for high inrush delays based on a 60Hz 1/2 cycle, 8.33 ms pulse.
DC
TRIP TIME IN SECONDS
AC
TRIP TIME IN SECONDS
Instantaneous
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Short
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Medium
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Long
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
E-Series Circuit Breaker - Time Delay Values | 11
AC/DC
TRIP TIME IN SECONDS
Instantaneous
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Short
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Medium
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Long
PERCENT OF RATED CURRENT
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
12 | Notes
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Reps & Contact | 13
Authorized Sales Representatives
Click on the group name on the map below to find your local representative or visit
www.carlingtech.com/findarep.
«
«
Matera
W. Canada
Matera
E. Canada
MIDWEST
DM
Michigan
TEMCO Northwest
Alaska, Hawaii
«
NORTHERN
Hanna Lind Ltd.
Melody
Emery
Sierra
Bridge Marketing
Omega Limited
Dy-tronix Inc.
LD. Allen
Norris
DM Assoc
East
Pacent
DM
Assoc
TSI North
TSI
WEST
Signal
Enterprises
Luscombe
Engineering
Pinnacle Marketing
Matrix
DM Mexico
South America
Mexico
«
«
Sunbelt Components
SOUTHEAST
ProRep
Solutions
LATIN AMERICA
Americas
Europe
Middle East
Africa
Asia-Pacific
Oceania
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-profile.
To view all of Carling’s environmental, quality, health & safety certifications please visit
www.carlingtech.com/environmental-certifications
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
Email: [email protected]
Northern Region Sales Office: [email protected]
Southeast Region Sales Office: [email protected]
Midwest Region Sales Office: [email protected]
West Region Sales Office: [email protected]
Latin America Sales Office: [email protected]
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
Email: [email protected]
Shenzhen, China: [email protected]
Shanghai, China: [email protected]
Pune, India: [email protected]
Kaohsiung, Taiwan: [email protected]
Yokohama, Japan: [email protected]