E-Series E-Series CIRCUIT BREAKER The E-Series hydraulic-magnetic circuit breaker is ideally suited for higher current and voltage applications. It is UL listed and CSA certified for branch circuit protection, which does not require a fuse back up. It is also UL recognized and CSA certified as a supplementary protector and as a manual motor controller. Its physical features include front and back mounting, screw and stud terminals and heavy duty box wire connectors for solid wire or a pressure plate connector for standard wire. The E-series is available with handle actuators and can be configured as .1-125 amps, up to 600VAC or 125VDC, with choice of time delays, actuator colors and 1 to 6 poles configuration. Additionally, a Power Selector device is also available. Product Highlights: UL listed and CSA certified Certified for circuit branch protection Recognized as a supplementary protector and as a manual motor controller Optional power selector device Typical Applications: High Voltage/High Current Applications Renewable Energy Military Industrial Controls Generators Carling Technologies, Inc. 60 Johnson Avenue, Plainville, CT 06062 Email: [email protected] Application Support: [email protected] Phone: 860.793.9281 Fax: 860.793.9231 www.carlingtech.com 2 | E-Series Circuit Breaker - General Specifications Electrical Maximum Voltage 600VAC 50/60 Hz, 125VDC (See Table A) Current Ratings Standard current coils: 0.100, 0.250, 0.500, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 50.0, 60.0, 70.0 & 100 Amp. Auxiliary Switch Rating SPDT; 10.1A 250VAC, 1.0A 65VDC; 0.5A 80VDC, 0.1A 125VAC (with gold contacts). Insulation Resistance Minimum of 100 Megohms at 500 VDC. Dielectric Strength UL, CSA: 2200 V 50/60 Hz for one minute between all electrically isolated terminals. E-Series Circuit Breakers comply with the 8mm spacing and 3750V 50/60 Hz dielectric requirements from hazardous voltage to operator accessible surfaces, between adjacent poles and from main circuits to auxiliary circuits per Publications EN 60950 and VDE 0805. Resistance, Impedance Values from Line to Load Terminal - based on Series Trip Circuit Breaker. CURRENT TOLERANCE (AMPS) (%) 0.10 - 5.0 5.1 - 20.0 ± 15 ± 25 20.1 - 50.0 ± 35 Mechanical Endurance 10,000 ON-OFF operations @ 6 per minute; with rated Current and Voltage. Trip Free All E-Series Circuit Breakers will trip on overload, even when Handle is forcibly held in the ON position. Trip Indication The operating Handle moves positively to the OFF position when an overload causes the breaker to trip. Physical Number of Poles Mounting Connectors, Box Type Internal Circuit Configuration Weight Standard Colors 1-6 A 3” minimum spacing must be provided between the circuit breaker arc venting area on back connected E-Series circuit breakers and grounded obstructions. E-Series circuit breakers must be mounted on a vertical surface. Front connected E-Series circuit breakers are supplied with box type pressure connectors that accept copper or aluminum conductors as follows: 1/0-14 Copper, 1/0-12 Aluminum. Series and Switch Only, (with or without auxiliary switch). Shunt with current coils. Approximately 252 grams/pole (Approximately 9 ounces/pole) Housing-Black; Actuator - See Ordering Scheme. Environmental Designed in accordance with requirements of specification MIL PRF-55629 & MIL-STD-202G as follows: Pulse Tolerance Curves Time Delay Curves 62, 64 & 66 (100 Amps Max.) Time Delay Curves 22, 24 & 26 (100 Amps Max.) Shock Withstands 100 Gs, 6ms, sawtooth while carrying rated current per Method 213, Test Condition “I”. Vibration Withstands 0.060” excursion from 10-55 Hz, and 10 Gs 55-500 Hz, at rated current per Method 204C, Test Condition A. Moisture Resistance Method 106D, i.e., ten 24-hour cycles @ + 25°C to +65°C, 80-98% RH. Salt Spray Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96 hrs). Thermal Shock Method 107D, Condition A (Five cycles @ -55°C to +25°C to +85°C to +25°C). Operating Temperature -40° C to +85° C *Manufacturer reserves the right to change product specification without prior notice. Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com E-Series Circuit Breaker - General Specifications | 3 Electrical Tables Table A: Lists UL Listed (489) & CSA Certified (C22.2 No. 5) configurations & performance capabilities as a Molded Case Circuit Breaker. E SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS VOLTAGE CIRCUIT CONFIGURATION SERIES CURRENT RATING MAX. RATING FREQUENCY PHASE FULL LOAD AMPS INTERRUPTING CAPACITY (AMPS) HIGH INTERRUPTING CAPACITY WITHOUT BACKUP (AMPS) FUSE 80 DC --- 0.10 - 100 5,000 50,000 125 DC --- 0.10 - 100 5,000 10,000 125 DC --- 0.10 - 125 10,000 --- 120 50 / 60 1 0.10 - 125 10,000 --- 240 240 50 / 60 50 / 60 1 1 0.10 - 30 31 - 100 5,000 5,000 10,000 120 / 240 50 / 60 1 0.10 - 30 5,000 10,000 120 / 240 50 / 60 1 31 - 100 5,000 --- 120 / 240 50 / 60 1 101 - 125 10,000 --- 240 50 / 60 3 0.10 - 100 5,000 --- Table B: Lists UL Recognized & CSA Accepted configurations & performance capabilities as a Component Supplementary Protector. E -SERIES TABLE B: COMPONENT SUPPLEMENTARY PROTECTORS CURRENT RATING SHORT CIRCUIT CAPACITY (AMPS) UL/CSA FULL LOAD GENERAL FREQUENCY PHASE WITH BACKUP WITHOUT AMPS PURPOSE AMPS FUSE3 BACKUP FUSE VOLTAGE CIRCUIT CONFIGURATION MAX. RATING APPLICATION CODES UL CSA 125 DC --- 0.02 - 100 --- --- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1 125 150 DC DC ----- ----- 101 - 120 0.02 - 125 ----- 5,000 5,000 TC1,2, OL0, U1 TC1,2, OL0, U1 TC1, OL0, U3 TC1, OL0, U3 160 150 / 300 DC DC ----- 0.02 - 100 0.02 - 100 ----- ----- 5,000 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1 TC1,2, OL1, U1 TC1,2, OL1, U1 SERIES & 120 / 240 50 / 60 1 --- 0.02 - 100 --- 5,000 TC1,2, OL0, U1 TC1,2, OL0, U1 SHUNT 240 250 50 / 60 50 / 60 1 1 0.02 - 100 0.02 - 100 ----- --10,000 5,000 --- TC1,2, OL1, U1 TC1,2, OL1, U1 TC1,2, OL1, C1 TC1,2, OL1, C1 277 50 / 60 1 0.02 - 100 --- --10,000 5,000 --- TC1,2, OL1, U1 TC1,2, OL1, U1 TC1,2, OL1, C1 TC1,2, OL1, C1 480 50 / 60 50 / 60 50 / 60 1&3 1&3 1&3 0.02 - 100 0.02 - 50 0.02 - 100 ------- 10,000 10,000 10,000 ------- TC1,2, OL1, C1 TC1,2, OL1, C1 TC1,2, OL1, C1 TC1,2, OL1, C1 TC1,2, OL1, C1 TC1,2, OL1, C1 DC --- --- 0.02 - 125 --- 5,000 DC --- 0.02 - 120 160 DC --- 0.02 - 100 240 277 50 / 60 50 / 60 1 1 0.02 - 100 0.02 - 100 480 600 50 / 60 50 / 60 1&3 1&3 0.02 - 100 0.02 - 100 480 1 600 600 2 125 SWITCH ONLY TC1, OL0, U3 Notes: 1 Per pole opposite polarity rating - Delta Configuration. 2 4 Poles connected in series 3 Requires branch circuit backup with a UL Listed Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amp rating and not to exceed 225A. Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com TC1, OL0, U3 4 | E-Series Circuit Breaker - General Specifications Electrical Tables Table C: Lists UL Recognized, CSA Accepted and VDE Certified configurations and performance capabilities as a Component Supplementary Protector. E -SERIES TABLE C: COMPONENT SUPPLEMENTARY PROTECTORS WITH VDE CURRENT RATING VOLTAGE CIRCUIT CONFIGURATION SHORT CIRCUIT CAPACITY (AMPS) UL/CSA MAX. FREQUENCY PHASE FULL LOAD AMPS WITH BACKUP RATING FUSE1 125 DC --- 0.1 - 100 --- WITHOUT BACKUP FUSE WITHOUT BACKUP FUSE 5,000 5,000 SERIES & 240 50 / 60 1&3 0.1 - 100 --- 5,000 5,000 SHUNT 415 50 / 60 1&3 0.1 - 100 10,000 --- 4,000 SWITCH ONLY 125 DC --- 0.1 - 125 240 50 / 60 1&3 0.1 - 100 415 50 / 60 1&3 0.1 - 100 APPLICATION CODES VDE (Icn) UL CONSTRUCTION NOTES CSA TC1,2, OL1, U1 TC1,2, OL1, U1 1 or 2 Poles 1 - 5 Poles. Up to 4 TC1,2, OL1, U1 TC1,2, OL1, U1 Current Poles, 1 Voltage Pole 2 - 5 Poles. Up to 4 TC1,2, OL1, C1 TC1,2, OL1, C1 Current Poles, 1 Voltage Pole Notes: 1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amp rating and not to exceed 225 amps. Table D: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors. E SERIES TABLE D : UL1500 (Marine Ignition Protection) VOLTAGE CIRCUIT CONFIGURATION SERIES MAX. RATING FREQUENCY CURRENT RATING SHORT CIRCUIT CAPACITY (AMPS) FULL LOAD AMPS WITHOUT BACKUP FUSE UL CSA PHASE 65 DC --- 0.02 - 100 5,000 TC1,2,OL1,U1 TC1,2,OL1,U1 125 50 / 60 1 0.02 - 100 1,500 TC1,2,OL1,U1 TC1,2,OL1,U1 250 50 / 60 1 0.02 - 100 1,500 TC1,2,OL1,U1 TC1,2,OL1,U1 Agency Certifications UL Recognized UL Standard 1077 UL Standard 1500 UL Listed UL Standard 489 APPLICATION CODES Component Recognition Program as Protectors, Supplementary (Guide QVNU2, File E75596) CSA Accepted Component Supplementary Protector (Class 3215 30, File 047848 0 000) CSA Standard C22.2 No. 235 Component Recognition Program as Manual Motor Controls (Guide NLRV2, File E135367) CSA Certified Circuit Breaker Molded Case (Class 1432 01, File 093910), CSA Standard C22.2 No. 5.1 - M Protectors, Supplementary for Marine Electrical & Fuel Systems (Guide PEQZ2, File E75596) Ignition Protection TUV Certified EN60934 under License No. R72031056 VDE Certified EN60934, VDE 0642 under File No. 10537 Circuit Breakers, Molded Case (Guide DIVQ, File E129899) Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com E-Series Circuit Breaker - Handle UL Recognized – Ordering Scheme | 5 E A 2 1 Series 2 Actuator B 0 4 Circuit 3 Poles 5 Auxiliary Switch 24 450 6 Frequency & Delay 7 Current Rating 2 ACTUATOR A Handle, one per pole 3Three 4Four 4 CIRCUIT 2 A 3 Switch Only (no coil) B Series Trip (current) C Series Trip (voltage) D Shunt Trip (current) 6 FREQUENCY & DELAY 03 3 DC 50/60Hz, Switch Only 10 5 DC Instantaneous 12 DC Short 14 DC Medium 16 DC Long 20 5 50/60Hz Instantaneous 22 50/60Hz Short 24 50/60Hz Medium 26 50/60Hz Long 30 DC, 50/60Hz Instantaneous 32 DC, 50/60Hz Short E F G Shunt Trip (voltage) Relay Trip (current) Relay Trip (voltage) S.P.S.T. 0.110 Q.C. Terminals S.P.S.T. 0.110 Q.C. Terminals (Gold Contacts) S.P.S.T. 0.187 Q.C. Terminals S.P.D.T. 0.187 Q.C. Terminals 34 DC, 50/60Hz Medium 36 DC, 50/60Hz Long 62 50/60Hz Short, Hi-Inrush 64 50/60Hz Medium, Hi-Inrush 66 50/60Hz Long, Hi-Inrush 72 DC, Short,Hi-Inrush 74 DC,Medium, Hi-Inrush 76 DC, Long, Hi-Inrush 92 6DC, 50/60Hz Short, Hi-Inrush 94 6DC, 50/60Hz Medium, Hi-Inrush 96 6DC, 50/60Hz Long, Hi-Inrush 11 Maximum Application Rating 0.350 0.400 0.450 0.500 0.550 0.600 0.650 0.700 0.750 0.800 0.850 0.900 0.950 1.000 1.250 1.500 1.750 2.000 2.250 2.500 2.750 430 435 440 445 450 455 460 465 470 475 480 485 490 495 610 710 611 711 612 712 613 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 10.500 11.000 11.500 12.000 12.500 13.000 OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS) 5 A06 6 DC, 5 DC A65 65 DC, 55 DC J48 A12 12 DC, 10 DC B25 125 DC, 100 DC J65 A18 18 DC, 15 DC J06 6 AC, 5 AC K20 A24 24 DC, 20 DC J12 12 AC, 10 AC L40 A32 32 DC, 25 DC J18 18 AC, 15 AC A48 48 DC, 40 DC J24 24 AC, 20 AC 614 615 616 617 618 620 622 624 625 630 635 640 650 660 670 680 690 810 811 812 912 8 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 50.000 60.000 70.000 80.000 90.000 100.000 110.000 120.000 125.000 48 AC, 40 AC 65 AC, 55 AC 120 AC, 65 AC 240 AC, 130 AC Notes: 1 VDE approval on 1-5 poles only. Standard multi-pole units identical poles except when specifying auxiliary switch - (see Note 4). For mixed ratings, consult factory. 2 Switch Only & Series Trip construction available with either front or back connected terminals. Shunt construction available with back connected terminals, (Terminal Codes 1 & 2) only. Circuit Codes B,C & D are VDE approved. 3 Switch Only construction: 30 amps or less select Current Rating Code 630; 31-70 amps, select Current Rating code 670; 71-100 amps, select Current Rating Code 810; 101-125 amps Select Current Rating Code 912. Switch Only is VDE approved only if tied to a protected pole. 12 Agency Approval MAX. RATING 50 A 120 A 50 A 100 A Dual Legend Color 1Black 2White 3White 4White 5White 6Black 7Black 8Black 10 MOUNTING / BARRIERS BACK CONNECTED (FRONT MOUNTED ONLY) Mounting Inserts A6-32 B ISO M3 CODEAMPERES 235 240 245 250 255 260 265 270 275 280 285 290 295 410 512 415 517 420 522 425 527 10 Mounting/ Barriers 9 ACTUATOR COLOR & LEGEND 13 Actuator Color I-O ON-OFF White AB Black CD Red FG Green HJ Blue KL Yellow MN Gray PQ Orange RS 7 CURRENT RATING (AMPERES) 7 0.020 0.025 0.030 0.035 0.040 0.045 0.050 0.055 0.060 0.065 0.070 0.075 0.080 0.085 0.090 0.095 0.100 0.150 0.200 0.250 0.300 9 Actuator Color FRONT CONNECTED (BACK MOUNTED ONLY) MAX. RATING 3 10 Box Wire Connector (Line & Load) 100 A 11 C Box Wire Connector with Pressure Plate (Line & Load) 100 A 4 10-32 Screw (Line & Load) 50 A D M5 Screw (Line & Load) 50 A 5 10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load) 50 A E M5 “Bus-Type” Screw (Line), 10-32 Screw (Load) 50 A 6 10 10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A F 11 10-32 “Bus-Type” Screw (Line), Box Wire Connector with Pressure Plate (Load) 100 A 7 1/4-20 Screw (Line & Load) 100 A G M6 Screw (Line & Load) 100 A 8 1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load) 100 A H M6 “Bus-Type” Screw (Line), M6 Screw (Load) 100 A 10 9 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A J 11 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector with Pressure Plate (Load) 100 A 5Five 6Six 5 AUXILIARY SWITCH 4 0 without Auxiliary Switch 6 2 S.P.D.T. 0.110 Q.C. Terminals 7 3 S.P.D.T. 0.139 Solder Lug 4 S.P.D.T. 0.110 Q.C. Terminals 8 (Gold Contacts) 9 020 025 030 035 040 045 050 055 060 065 070 075 080 085 090 090 210 215 220 225 230 8 Terminal C B 8 TERMINAL 12 BACK CONNECTED (FRONT MOUNTED ONLY) 1 9 10-32 Stud (All Terminals) 2 9 1/4-20 Stud (All Terminals) A 9 M5 Stud (Line & Load) B 9 M6 Stud (Line & Load) 1 SERIES E 3 POLES 1 1 One 2Two 1 2 A FRONT CONNECTED (BACK MOUNTED ONLY) 14 Back Mounting Foot Type Front Mounting Inserts (Optional Use) CShort 6-32 D Short ISO M3 ELong 6-32 F Long ISO M3 11 MAXIMUM APPLICATION RATING 15 A 65 VDC, 120 A G 16 B 125 VDC, 120 A H 16 C 120/240 VAC, 100 A J 16 D 240 VAC, 100 A L 16 E 16 277/480 VAC, 100 A T F 277 VAC, 100 A W 16 600 VAC, 100 A 480 VAC, 100 A 415 VAC, 100 A 160 VDC, 100 A 125 VDC/240 VAC, 100 A 125 VDC/415 VAC, 100 A 12 AGENCY APPROVAL B UL 1077 / UL508 Recognized & CSA Accepted D UL 1077 Recognized, CSA Accepted, & VDE Certified 4 5 6 7 8 9 10 11 12 13 14 15 16 Auxiliary Switch available on Switch Only and Series Trip units. On multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme right pole. Back mounted units require special mounting provisions when auxiliary switch is specified. VDE approval on Auxilary Switch Codes 0,2,3 & 4 only. Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay Codes 10 & 20. Series Trip construction with a voltage coil s VDE approved only if tied to a protected pole. Frequency & Delay Codes 92,94 & 96 are not VDE Certified. Current Coil Ratings 0.100 - 100 ams are VDE Certified. 125 A rating (Code 912) available as a Switch Only (Circuit Code A), rated 125 VDC (Code B). An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 (Terminal Code 1). 1/4-20 (Code 2), M5 (Code A), and M6 (Code B) terminals per UL requirement. Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG. aluminum wire. Box Wire Connector with Pressure Plate for stranded wire, consult factory for details. Terminal Codes A,B,D,E,G & H are not VDE Certified. VDE approvals require Dual (I-O, ON-OFF) or I-O markings on all handles. Back Mounted breakers can also be front mounted by utilizing the proper front panel mounting inserts normally supplied. However, terminal connections must be made prior to mounting. Application ratings B,D,J,T & W are available with VDE. 415, 480 & 600 VAC ratings require 3 or 4 pole break 3Ø and 2 pole break 1Ø. Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 6 | E-Series Circuit Breaker - Handle UL Listed – Ordering Scheme E A 2 1 Series 2 Actuator 24 450 6 Frequency & Delay 7 Current Rating B 0 4 Circuit 3 Poles 5 Auxiliary Switch 2 ACTUATOR A Handle, one per pole 3 POLES 1 1 One 2Two 3Three 4Four 5Five 6Six 4 CIRCUIT 2 B Series Trip (current) C 3 Series Trip (voltage) 5 AUXILIARY SWITCH 4 0 without Auxiliary Switch 6 2 S.P.D.T. 0.110 Q.C. Terminals 7 3 S.P.D.T. 0.139 Solder Lug 4 S.P.D.T. 0.110 Q.C. Terminals 8 (Gold Contacts) 9 S.P.S.T. 0.110 Q.C. Terminals S.P.S.T. 0.110 Q.C. Terminals (Gold Contacts) S.P.S.T. 0.187 Q.C. Terminals S.P.D.T. 0.187 Q.C. Terminals 6 FREQUENCY & DELAY 10 5 DC Instantaneous 62 50/60Hz Short, Hi-Inrush 12 DC Short 64 50/60Hz Medium, Hi-Inrush 14 DC Medium 66 50/60Hz Long, Hi-Inrush 16 DC Long 72 DC, Short,Hi-Inrush 20 5 50/60Hz Instantaneous 74 DC,Medium, Hi-Inrush 22 50/60Hz Short 76 DC, Long, Hi-Inrush 24 50/60Hz Medium 26 50/60Hz Long 7 CURRENT RATING (AMPERES) 7 CODEAMPERES 0.020 0.025 0.030 0.035 0.040 0.045 0.050 0.055 0.060 0.065 0.070 0.075 0.080 0.085 0.090 0.095 0.100 0.150 0.200 0.250 0.300 9 Actuator Color 10 Mounting/ Barriers 8 TERMINAL 7 BACK CONNECTED (FRONT MOUNTED ONLY) 1 8 10-32 Stud (All Terminals) 2 8 1/4-20 Stud (All Terminals) 1 SERIES E 020 025 030 035 040 045 050 055 060 065 070 075 080 085 090 090 210 215 220 225 230 1 2 A 8 Terminal 235 240 245 250 255 260 265 270 275 280 285 290 295 410 512 415 517 420 522 425 527 0.350 0.400 0.450 0.500 0.550 0.600 0.650 0.700 0.750 0.800 0.850 0.900 0.950 1.000 1.250 1.500 1.750 2.000 2.250 2.500 2.750 430 435 440 445 450 455 460 465 470 475 480 485 490 495 610 710 611 711 612 712 613 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 10.500 11.000 11.500 12.000 12.500 13.000 OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS) 5 A06 6 DC, 5 DC A65 65 DC, 55 DC J48 A12 12 DC, 10 DC B25 125 DC, 100 DC J65 A18 18 DC, 15 DC J06 6 AC, 5 AC K20 A24 24 DC, 20 DC J12 12 AC, 10 AC L40 A32 32 DC, 25 DC J18 18 AC, 15 AC A48 48 DC, 40 DC J24 24 AC, 20 AC 614 615 616 617 618 620 622 624 625 630 635 640 650 660 670 680 690 810 811 812 912 8 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 50.000 60.000 70.000 80.000 90.000 100.000 110.000 120.000 125.000 48 AC, 40 AC 65 AC, 55 AC 120 AC, 65 AC 240 AC, 130 AC C C 11 Maximum Application Rating 12 Agency Approval MAX. RATING 50 A 125 A FRONT CONNECTED (BACK MOUNTED ONLY) MAX. RATING 3 9 Box Wire Connector (Line & Load) 100 A C 10 Box Wire Connector with Pressure Plate (Line & Load) 100 A 4 10-32 Screw (Line & Load) 50 A 5 10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load) 50 A 6 9 10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A F 10 10-32 “Bus-Type” Screw (Line), Box Wire Connector with Pressure Plate (Load) 100 A 7 1/4-20 Screw (Line & Load) 125 A 8 1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load) 100 A 9 9 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A J 10 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector with Pressure Plate (Load) 100 A 9 ACTUATOR COLOR & LEGEND 12 Actuator Color ON-OFF Dual Legend Color White B1Black Black D2White Red G3White Green J4White Blue L5White Yellow N6Black Gray Q7Black Orange S8Black 10 MOUNTING / BARRIERS BACK CONNECTED (FRONT MOUNTED ONLY) Mounting Inserts A6-32 B ISO M3 FRONT CONNECTED (BACK MOUNTED ONLY) 11 Back Mounting Foot Type Front Mounting Inserts (Optional Use) CShort 6-32 D Short ISO M3 ELong 6-32 F Long ISO M3 11 MAXIMUM APPLICATION RATING 15 1 120 VAC B 125 VDC, 120 A 13 C 120/240 VAC, 100 A D 240 VAC, 100 A 12 AGENCY APPROVAL C UL 489 Listed & CSA Certified F UL 489 Listed, CSA Certified, & VDE Certified Notes: 1 Standard multi-pole units identical poles except when specifying auxiliary switch (see Note 4). For mixed ratings, consult factory. VDE Certification on 1-5 poles only. 2 Series Trip construction available with either front or back connected terminals. 3 Series Trip construction with a voltage coil is not available as a single pole unit and must be tied to a protected pole. 4 On multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme right pole per Figure A. Back mounted units require special mounting provisions when auxiliary switch is specified. VDE Certification on auxilary switch codes 0, 2, 3 & 4 only. 5 Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay Codes 10 & 20. 6 Frequency & Delay Codes 92, 94 & 96 are not VDE Certified. 7 Current Ratings under 0.100 amps are not VDE Certified . 8 An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 Stud (Terminal Code 1) or 1/4-20 Stud (Code 2) terminals per UL requirement. 9 Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG. aluminum wire. 10 Box Wire Connector with Pressure Plate for stranded wire, consult factory for details. 11 Back Mounted breakers can also be front mounted by utilizing the proper front panel mounting inserts normally supplied. However, terminal connections must be made prior to mounting. 12 VDE Certification requires dual (I-O , ON-OFF) markings on all handles. 13 Not available with VDE Certification. Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com E-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams | 7 Circuit & Terminal Diagrams: in. [mm] Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 0-50 amps: 10-32 & M5 Studs .625±.062/15.88±1.574 long. 4 51-120 amps: 1/4-20 & M6 Studs .750±.062/19.05±1.574 long. Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 8 | E-Series Circuit Breaker - Handle (Back Connected) – Dimensional Specifications Dimensional Specifications: in. [mm] Notes: 1 1/4 -20 stud terminal in Series Trip circuit configuration shown. 2 A 3” min spacing must be provided between the circuit breaker arc venting area of back connected E-Series circuit breaker and grounded obstructions. 3 All dimensions are in inches [millimeters]. 4 Tolerance ±.020 [.51] unless otherwise specified. 5 Circuit breakers must be mounted on vertical surface. Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com E-Series Circuit Breaker - Handle (Front Connected) – Dimensional Specifications | 9 Dimensional Specifications: in. [mm] Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Box wire connector terminal in Series Trip circuit configuration shown. 4 Circuit breakers must be mounted on vertical surface. Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 10 | E-Series Circuit Breaker - Time Delay Values NOTES Delay Curves 10,20,30: Breakers to hold 100% and must trip at 150% of rated current and greater wthin the time limit shown in these curves. Delay Curves 12,14,16,22,24,26,62,64,66,72,74,76: Breakers to hold 100% and must trip at 125% of rated current and greater wthin the time limit shown in these curves. Delay Curves 32,34,36,92,94,96: Breakers to hold 100% and must trip at 135% of rated current and greater wthin the time limit shown in these curves. All curves: Data shown represents breaker response at ambient temperature of 77°F (25°C) with no preloading: Breakers are mounted in standard wall-mount position. The minimum inrush pulse tolerance handling capacity on the above standard delays is 16 times rated current &20 times rated current for high inrush delays based on a 60Hz 1/2 cycle, 8.33 ms pulse. DC TRIP TIME IN SECONDS AC TRIP TIME IN SECONDS Instantaneous PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT TRIP TIME IN SECONDS TRIP TIME IN SECONDS Short PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT TRIP TIME IN SECONDS TRIP TIME IN SECONDS Medium PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT TRIP TIME IN SECONDS TRIP TIME IN SECONDS Long PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com E-Series Circuit Breaker - Time Delay Values | 11 AC/DC TRIP TIME IN SECONDS Instantaneous PERCENT OF RATED CURRENT TRIP TIME IN SECONDS Short PERCENT OF RATED CURRENT TRIP TIME IN SECONDS Medium PERCENT OF RATED CURRENT TRIP TIME IN SECONDS Long PERCENT OF RATED CURRENT Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 12 | Notes Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Reps & Contact | 13 Authorized Sales Representatives Click on the group name on the map below to find your local representative or visit www.carlingtech.com/findarep. « « Matera W. Canada Matera E. Canada MIDWEST DM Michigan TEMCO Northwest Alaska, Hawaii « NORTHERN Hanna Lind Ltd. Melody Emery Sierra Bridge Marketing Omega Limited Dy-tronix Inc. LD. Allen Norris DM Assoc East Pacent DM Assoc TSI North TSI WEST Signal Enterprises Luscombe Engineering Pinnacle Marketing Matrix DM Mexico South America Mexico « « Sunbelt Components SOUTHEAST ProRep Solutions LATIN AMERICA Americas Europe Middle East Africa Asia-Pacific Oceania About Carling Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide, Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical components, they engineer powerful solutions! To learn more about Carling please visit www.carlingtech.com/company-profile. To view all of Carling’s environmental, quality, health & safety certifications please visit www.carlingtech.com/environmental-certifications Email: [email protected] Application Support: [email protected] Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Worldwide Headquarters Carling Technologies, Inc. 60 Johnson Avenue, Plainville, CT 06062 Phone: 860.793.9281 Fax: 860.793.9231 Email: [email protected] Northern Region Sales Office: [email protected] Southeast Region Sales Office: [email protected] Midwest Region Sales Office: [email protected] West Region Sales Office: [email protected] Latin America Sales Office: [email protected] Asia-Pacific Headquarters Carling Technologies, Asia-Pacific Ltd., Kowloon, Hong Kong Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332 Email: [email protected] Shenzhen, China: [email protected] Shanghai, China: [email protected] Pune, India: [email protected] Kaohsiung, Taiwan: [email protected] Yokohama, Japan: [email protected] Europe | Middle East | Africa Headquarters Carling Technologies LTD 4 Airport Business Park, Exeter Airport, Clyst Honiton, Exeter, Devon, EX5 2UL, UK Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477 Email: [email protected] Germany: [email protected] France: [email protected] www.carlingtech.com REV_02_2016