WRA120 SERIES 3PH AC - DC DIN RAIL MOUNTABLE 120W INDUSTRIAL CONTROL EQUIPMENT FEATURES 3 PHASE AC INPUT VOLTAGE COMPACT DESIGN HIGH EFFICIENCY UP TO 89% SELECTION CHART WRA 120 - 24 Wattage 12 : 12V OUT 24 : 24V OUT MODEL LIST MODEL NO. INPUT VOLTAGE WRA120-12 3o 340~575VAC 120 WATTS WRA120-24 3o 340~575VAC 120 WATTS OUTPUT OUTPUT WATTAGE VOLTAGE Single Output Models OUTPUT CURRENT EFF. (min.) EFF. (typ.) + 12 VDC 10A 85% 87% + 24 VDC 5A 87% 89% max. max. unit unit SPECIFICATION All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed GENERAL Conditions Conditions Characteristics min. min. Isolation voltage Input / Output Isolation resistance Input / Output, @ 500VDC 100 Ambient temperature Operating at Vi nom -25 typ. typ. 3,000 o VAC M + 71 o 2.5 o Derating Vi nom, from +61 to +71 C Storage temperature Non operational -25 + 85 Relative humidity Vi nom, Io nom 20 95 Dimension Screw terminal type L123.6 x W74.3 x D118.2 Cooling Free air convection Case material Metal www.chinfa.com 2008.08.13 C %/ C o C % RH mm [email protected] WRA120 SERIES SPECIFICATION All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed INPUT SPECIFICATIONS Characteristics Conditions typ. min. Nominal Voltage *1 unit 1o or 3o 380 / 480 VAC 400 Rated input voltage Io nom Input voltage range Ta min ... Ta max, Io nom Rated input current max. Io nom 500 VAC AC IN 340 575 VAC DC IN 480 820 VDC Vi : 380VAC 0.5 A Vi : 500VAC 0.35 A Line frequency Vi nom, Io nom Inrush current Vi nom, Io nom 10 P. F. C. Vi : 500VAC, Io nom 0.6 47 63 Hz A OUTPUT SPECIFICATIONS Characteristics Output voltage accuracy Conditions typ. min. max. unit + 1 % (Adjusted before shipment) Vi nom, Io max Minimum load Vi nom Line regulation Io nom, Vi min ...Vi max 1 % Load regulation Vi nom, Io min ...Io nom single mode 1 % Temperature coefficient Vi nom, Io min 0.02 % / oC Ripple & noise Vi nom, Io nom,BW = 20MHz 100 mV -0 % 0 Hold up time Vi nom, Io nom Voltage trim range Vi nom, Io nom DC ON indicator threshold at start up Vi nom, Io nom DC LOW indicator threshold at start up Vi nom, Io nom Efficiency Vi nom, Io nom, Po / Pi 16 20 ms 12V model 11.4 14.5 VDC 24V model 22.5 28.5 VDC 12V model 10 11.2 VDC 24V model 17.6 19.4 VDC 12V model 10 11.2 VDC 24V model 17.6 19.4 VDC Up to 89% CONTROL AND PROTECTION Characteristics Conditions min. typ. max. unit 2A / 600VAC internal / phase Input fuse Rated over load protection Vi nom 115 135 % Power Rdy (for 24V model only) Threshold voltage of contact closed(at start up) 17.6 19.4 VDC Electrical isolation 500 Contact rating at 60VDC Over voltage protection Vi nom, Io nom Output short circuit Vi nom Over temperature Detect on heatsink, shut down O/P voltage, recovers automatically after temperature goes down. 12V model 24V model VDC 0.3 A 14.5 17.4 V 30 33 V Current limited 100 110 o C *1. Single phase input is permissible, but output is derated to 75%. www.chinfa.com 2008.08.13 [email protected] WRA120 SERIES SPECIFICATION All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed APPROVALS AND STANDARDS UL / cUL UL508 Listed, UL60950-1 Recognized TUV EN60950-1 CE EN61000-6-3, EN55022 class B EN61000-3-2, EN61000-3-3 EN61000-6-2, EN55024 EN61204-3 CIRCUIT SCHEMATIC Block diagram for WRA120 series L1 Fuse1 L2 Fuse2 L3 Fuse3 Vo + X Filter X X Bridge Rectifier Filter P.F.C Circuit Switching Device Rectifier Vo - PWM Controller Y Opto Isolation Reference & Error Amp. Opto Isolation Over Voltage Detection Output Level Detection Note: 1) For 24V Model Only Vout ADJ. DC ON (Green LED) DC LOW (Red LED) RDY 1) (Relay Contact) PHYSICAL CHARACTERISTICS CASE SIZE SCREW TERMINAL TYPE 123.6 x 74.3 x 118.2 mm (4.87 x 2.92 x 4.65 inches) WEIGHT 800g DERATING Power out [ % ] 100 75 0 -25 www.chinfa.com 2008.08.13 Temperature [ oC ] 61 71 [email protected] WRA120 SERIES MECHANISM & PIN CONFIGURATION mm [inch] CONSTRUCTION 74.3 [2.92] 9 10 1 Easy snap-on mounting onto the DIN-Rail (TS35/7.5 or TS35/15), unit sits safeIy and firmly on the rail. 111.3 [4.38] 106.6 [4.2] 4 6.9 [0.27] + + 123.6 [4.87] INSTALLATION Ventilation / Cooling Normal convection All sides 25mm free space For cooling recommended Connector size range 10-24AWG flexible / solid cable, 8 m/m stripping at cable end recommends R WRA120 L1 L2 L3 5 8 PIN ASSIGNMENT Designation PIN NO. Description V+ Positive output terminal 2 V+ Positive output terminal V - Negative output terminal V - Negative output terminal 3 OUT 1 4 Ground this terminal to minimize high-frequency emissions 5 Input terminals L2 Input terminals 8 L3 Input terminals 9 RDY RDY A normal open relay contact for DC ON level control (Never connect except 24V model) DC ON Operation indicator LED DC LO DC LOW voltage indicator LED Vout ADJ. Trimmer-potentiometer for Vout adjustment 10 www.chinfa.com 2008.08.13 OTHER OUT 7 IN L1 6 [email protected]