CRYDOM DRA4D100D12

DRA4D Series
• DC Motor Reversing Contactor
• Ratings of 6 & 12 Amps
• Load voltage ratings of 1-100VDC and 1-250VDC
• Fits standard 35mm DIN-RAIL
• LED input status indicator. Green (Forward), Yellow (Reverse)
• DC control
• cUL Recognized, IEC Rated, CE & RoHS Compliant
• Horsepower Rated
PRODUCT SELECTION
Description
5-15 VDC Control
15-32 VDC Control
12A
6A
DRA4D100D12
DRA4D100E12
DRA4D250D6
DRA4D250E6
DRA4D100x12
DRA4D250x6
1-100 (3)
12
1.0
1.0
0.1
110
0.011
1-250 (2)
6 (5)
1.0
20
0.1
91
0.45
0.48
24/10
0.5-4.0
1/4, 4 FLA @ 90 VDC
12 FLA @ 90 VDC, 1KW
4.0 FLA @ 90 VDC, 360W
0.45
24/10
0.5-4.0
1/4, 2 FLA @ 180 VDC
6.0 FLA @ 180 VDC, 1KW
2.0 FLA @ 180 VDC, 360W
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage [VDC]
Maximum Load Current [Adc] (4)
Minimum Load Current [mAdc]
Maximum Off-State Leakage Current @ Rated Voltage [uA]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum Surge Current (10ms) [Apk]
On-State resistance at rated current (RDSOn) [Ohms]
Thermal Resistance Junction to Case (Rjc) [°C/W]
Min/Max stranded/solid wire [AWG]
Min/Max stranded/solid wire [IEC mm²]
HP Rating per UL508 @ 40°C
IEC 60947-4-1 Ratings DC-1
IEC 60947-4-1 Ratings DC-3
INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
Minimum Turn-On Voltage
Minimum Turn-Off Voltage
Minimum Input Current [mA]
Maximum Input Current [mA]
Nominal Input Impedance
Maximum Turn-On Time [msec]
Maximum Turn-Off Time [msec]
Min/Max stranded/solid wire
Min/Max stranded/solid wire [IEC mm²]
DRA4DxxxD
DRA4DxxxE
5.0-15 VDC
5.0 VDC
2.5 VDC
16
24.5
See Note 6
22
0.264
24/12
0.5-2.5
15-32 VDC
15 VDC
2.9 VDC
20.5
22
See Note 6
22
0.33
24/12
0.5-2.5
GENERAL SPECIFICATIONS
Description
Dielectric Strength, Input/Output/Base (50/60Hz)
Minimum Insulation Resistance (@ 500 V DC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Recommended Terminal Screw Torque:
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) UL maximum rated voltage is 180VDC
3) UL maximum rated voltage is 90VDC.
4) At 40°C and mounted in vertical position
5) At 40°C single unit, multiple units need spacing of 45mm.
No spacing maximum current is 5.5A
6) Input circuitry incorporates active current limiter.
MECHANICAL SPECIFICATIONS
Parameters
2500Vrms
109 Ohms
35 pF @ 1KHz
-30ºC to 60ºC
-30ºC to 85ºC
4.0 in lb (0.45 Nm)
WIRING DIAGRAM
THERMAL DERATE INFORMATION
AGENCY APPROVALS
Designed in accordance with the requirements of IEC 62314
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 2 (Criteria A)
IEC 61000-4-5 : Electrical Surges - Level 2 (Criteria A)
E116949
Rev 111011