FUJI EDSX6-102

FCX – AX SERIES
FLOW TRANSMITTER
FHF...3
DATA SHEET
The FCX–AX flow transmitter accurately measures
differential pressure generated by a primary element, and
transmits a 4 to 20mA signal proportional to flow. The
transmitter utilizes unique micromachined capacitance silicon
sensor with state-of-the-art microprocessor technology to
provide exceptional performance and functionality.
FEATURES
1. High accuracy
0.07% accuracy for all calibrated spans is a standard
feature for all models covering 0.1kPa{1mbar} draft range
to 3000kPa{30bar} high differential. Fuji's microcapacitance silicon sensor assures this accuracy.
2. Minimum environmental influence
The "Advanced Floating Cell" design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
3. Application flexibility
Various options that render the FCX–AX suitable for
almost any process applications include:
– Analog indicator at either the electronics side or
terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 4 12 -digits LCD meter
– Stainless steel electronics housing
– Wide selection of materials
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Static pressure
[MPa] {bar}
Type
FHF 11
FHF 22
FHF 23
FHF 25
FHF 26
FHF 33
FHF 35
FHF 36
FHF 38
FHF 43
FHF 44
FHF 45
FHF 46
FHF 48
–
–
–0.1 to + 3.2
{–1 to + 32 }
–0.1 to + 10
{–1 to + 100 }
–0.1 to + 10
{–1 to + 100 }
–0.1 to + 10
{–1 to + 100 }
–0.1 to + 10
{–1 to + 100 }
–0.1 to + 16
{–1 to + 160 }
–0.1 to + 16
{–1 to + 160 }
–0.1 to + 16
{–1 to + 160 }
–0.1 to + 16
{–1 to + 160 }
–0.1 to + 42
{–1 to + 420 }
–0.1 to + 42
{–1 to + 420 }
–0.1 to + 42
{–1 to + 420 }
–0.1 to + 42
{–1 to + 420 }
–0.1 to + 42
{–1 to + 420 }
{
{
{
{
{
{
{
{
{
{
{
{
{
{
Span limit [kPa]
{m bar}
Max.
Min.
0.1
1
1}
{
10 }
0.6
6
6}
{
60 }
3.2
32
32 }
{
320 }
13
130
130 }
{ 1300 }
50
500
500 }
{ 5000 }
3.2
32
32 }
{
320 }
13
130
130 }
{ 1300 }
50
500
500 }
{ 5000 }
300
3000
3000 }
{ 30000 }
6.4
64
32 }
{
320 }
6.4
64
64 }
{
640 }
13
130
130 }
{ 1300 }
50
500
500 }
{ 5000 }
300
3000
3000 }
{ 30000 }
Range limit
[kPa] {m bar}
+/–
1
{ +/–
10 }
+/–
6
{ +/–
60 }
+/–
32
{ +/–
320 }
+/–
130
{ +/– 1300 }
+/–
500
{ +/– 5000 }
+/–
32
{ +/–
320 }
+/–
130
{ +/– 1300 }
+/–
500
{ +/– 5000 }
+/– 3000
{ +/– 30000 }
+/–
32
{ +/–
320 }
+/–
64
{ +/–
640 }
+/–
130
{ +/– 1300 }
+/–
500
{ +/– 5000 }
+/– 3000
{ +/– 30000 }
Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor: See Fig. 1
FHF 38 and FHF 48: –50kPa{–0.5kgf/cm2}
Fluorinated fill sensor: 66kPa abs (500mmHg abs)
at temperature below 60°C.
The maximum span of each sensor can be converted to
different units using below factors.
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
EDSX6-102
Date
Mar. 15, 1999
FHF...3
Overrange limit: To maximum static pressure limit
Output signal:
4 to 20mA DC
Square root of differential input pressure
between 0.5% and 100% of input.
Linear or zero is selectable below 0.5%
of input.
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
Load limitations: see figure below
“Output Hold”: Output signal is hold as the value just
before failure happens.
“Output Overscale”: Approx. 21.6mA
“Output Underscale”: Approx. 3.8mA
3.2
3.8 4
20 20.8
Over scale
Burnout
0
Normal operating range
Under scale
Probable under range
Burnout
21.6
Probable over range
[Ω]
Load resistance
2000
1533Ω
1500
1000
600Ω
Operating
area
500
24V
250
10
16.1
10.5V
Power voltage
45V
50
[V]
Hazardous locations: (Approval pending)
Authorities
BASEEFA
Factory
Mutual
CSA
RIIS
SAA
Flameproof
Ex ds IIC T5, T6
Class I II III
Div. 1
Groups B thru. G
Class I II III
Div. 1
Groups C thru. G
Ex ds IIB+H2 T4
Ex d II C T5, T6
IP 66/67
Intrinsic safety
EEx ia IIC T4, T5
Class I II III
Div. 1
Groups A thru. F
Class I II III
Div. 1
Groups A thru. G
—
Ex ia II C T5, T6
IP 66/67
Type N
Nonincendive
Ex N II T5
Class I II III
Div. 2
Groups A thru. G
Class I II III
Div. 2
Groups A thru. G
—
Ex n II C T5, T6
IP 66/67
Zero/span adjustment:
Zero is adjustable from the external adjustment screw.
The adjustment screw can also function to
adjust span when MODE SWITCH (located on the electronics unit) is in the span
mode.
INHIBIT mode to disable the adjustable
screw is also available.
Damping:
Adjustable electrical damping.
The time constant is adjustable to 0, 0.3,
1.2, 4.8, or 19.2 seconds.
Zero elevation/suppression:
–100% to +100% of URL
Normal/reverse action:
Selectable by moving a jumper pin located
on the electronics unit.
Indication:
Analog indicator or 4 12 -digit LCD meter, as
specified.
Burnout direction: If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
Model FHF: Unless otherwise specified in the order,
the transmitter will be shipped in “Output
Hold” mode.
(Output signal just before failure happens
is maintained.)
2
Loop-check output:
Transmitter can output constant signal of
4mA, 12mA, or 20mA if MODE SWITCH
is set to the loop check mode.
Temperature limit: Ambient: – 40 to + 85°C
(– 20 to + 80°C for LCD indicator)
(– 40 to + 60°C for arrester option)
(– 10 to + 60°C for fluorinated oil fill
transmitter)
– 15 to +85°C for 6 digit code “8”.
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified in
each standard.
Process: – 40 to +120°C for silicone fill
sensor
– 20 to +80°C for fluorinated oil fill sensor
Storage: – 40 to +90°C
Humidity limit:
0 to 100% RH
Performance specifications
Accuracy rating: (Including linearity, hysteresis, and repeatability)
Max span above 32kPa model:
± 0.07% of calibrated span for a range of
50% to 100% of flow.
(± 0.175% for a range of 20% to 50% of
flow)
Max span 1kPa, 6kPa model:
± 0.1% of calibrated span for a range of
50% to 100% of flow.
(± 0.25% for a range of 20% to 50% of
flow)
Stability:
± 0.1% of upper range limit (URL) for 24
months
Temperature effect:
Effects per 55°C change between the limits of – 40°C and +85°C
Shift at 20% output
(% of URL)
Range code
(6th digit in "Code symbols")
“1”/
“2”/
1kPa (10m bar} max. span
6kPa (60m bar} max. span
“3”/ 32kPa
“4”/ 64kPa
“5”/ 130kPa
“6”/ 500kPa
“8”/ 3000kPa
{320m bar} max. span
{640m bar} max. span
{1300m bar} max. span
{5000m bar} max. span
{30000m bar} max. span
± 0.3+0.25
(
URL
%/28°C
Span
)
± 0.25+0.0625 URL %/28°C
Span
(
)
Static pressure effect:
Physical specifications
Static pressure code
(5th digit in "Code symbols")
Shift at 20% output
(% of URL)
± 0.25%/1MPa{10bar}
± 0.25%/3.2MPa{32bar}
“1” /1kPa {10m bar} sensor
“2” /6kPa {60m bar} sensor
“2”
“3”
“4”
± 0.125%/10MPa{100bar}
Double the shift for material code (7th digit in Code symbols) “H”, “M”, “T”, “B”, “L” and “U”.
Overrange effect: Shift at 20% output (% of URL)
Shift at 20% output
(% of URL)
Static pressure code
(5th digit in "Code symbols")
± 0.75% / 1MPa
± 0.75% /3.2MPa
± 0.25% / 10MPa
± 0.25% / 16MPa
± 0.42% / 42MPa
“1” / 1kPa {10m bar} sensor
“2” / 6kPa {60m bar} sensor
“2”
“3”
“4”
{10bar }
{32bar }
{100bar } 
{160bar }  *1
{420 bar} 
Double the effects for material code “H”, “M”, “T”, “B”,
“L” and “U”.
*1) In case of 6th code “5”.
Supply voltage effect:
Less than 0.05% of calibrated span per
10V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Step response: (without electrical damping)
Type
Time constant
FHF
11
1.25 s
FHF
12
0.85 s
FHF
3
FHF
4 to
0.45 s
8
Dead time
approx. 0.3 s
0.2 s
Mounting position effect:
Zero shift, less than 0.12kPa {1.2m bar} for
a 10° tilt in any plane.
No effect on span.
This error can be corrected by adjusting
Zero.
(Double the effect for fluorinated fill sensors)
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
Meets DIN 19213.
Process-wetted parts material:
Material
code
(7th figure Process cover
in "Code
symbols")
V
H
M
T
B
L
U
316 stainless
steel(*1)
316 stainless
steel(*1)
316 stainless
steel(*1)
316 stainless
steel(*1)
Hastelloy-C
lining
Monel lining
Tantalum
lining
Diaphragm
Wetted
sensor body
316L stainless 316 stainless
steel
steel
Hastelloy-C
Hastelloy-C
lining
Monel
Monel lining
Tantalum
Tantalum
lining
Hastelloy-C
lining
Monel lining
Tantalum
lining
Hastelloy-C
Monel
Tantalum
Vent/drain
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
Hastelloy-C
Monel
Tantalum
Notes: * (1) SCS14 per JIS G 5121
Remark: Sensor O-rings: Viton and teflon selectable.
Availability of above material design depends on ranges and static
pressure. Refer to “Code symbols”.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy (standard), finished
with polyester coating, or 316 stainless
steel (SCS14 per JIS G5121), as specified.
Bolts and nuts: Cr-Mo alloy (standard), 304
stainless steel (for static pressure code
“1”, “2”, and “3” only), or 630 stainless steel (for static pressure code "4"
only). Static pressure rating for code
“3” with 304 stainless steel bolts is degraded to 10MPa{100bar}.
Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil)
Mounting bracket: Carbon steel with epoxy coating or 304 stainless steel, as
specified
Environmental protection:
IEC IP67 and NEMA 4X
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting, or direct
process mounting.
Mass{weight}:
Transmitter approximately 4.4kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
3
FHF...3
Optional features
ACCESSORIES
Indicator:
A plug-in analog indicator (1.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 4 digits LCD meter is also
available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4KV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
ASTM B7M or12 L7M bolts and 2HM nuts
(Class II) are available.
Static pressure rating for code “3” (160
bar) is degraded to 100 bar.
Vacuum service: Special silicone oil and filling procedure
are applied.
See below figure.
Sealing liquid:Silicone oil (Code:Y,G,N)
Sealing liquid:Silicone oil (Code:R)
Operating pressure
[kPa abs]
{mbar abs}
101
{1010}
53.3
{533}
Operating
area
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Three-value manifolds:
(Model FFN, refer to Data Sheet No.
EDS6-10)
Available in carbon steel or in 316 stainless steel and in pressure rating 16MPa
{160bar} or 42MPa{420bar}.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510412. The applicable standards used to demonstrate
compliance are :EMI (Emission)
EN50081-1 : 1992
Test item
Frequency range
Basic standard
Applicable Electromagnetic Radiation
Disturbance
30-1000MHz
EN55022
Class B
EMS (Immunity)
EN50082-1 : 1992
No.
Test item
Test
specification
Basic
standard
Performance
criteria
1
Electrostatic
discharge
8kV (Air)
IEC 801-2:1984
B
2
Radio-frequency 27-500MHz
electromagnetic 3V/m
IEC 801-3:1984
field.
(Unmodulated)
A
3
Fast transients
common mode
0.5kV, 5/50
(Tr/Th) ns
5kHz Rep.
IEC 801-4:1988
B
"LVD - The transmitter is not covered by the requirements
of the LVD standard."
6.7
{67}
2.7
{27}
–40
–15
60 85 120
Process temperature[°C ]
Fig. 1 Relation between process temperature and
operating pressure
Customer tag:
Coating of cell:
4
Oval flanges:
A stainless steel tag with customer tag
data is wired to the transmitter.
Cell's surface is finished with epoxy/
polyuretane double coating.
Specify if environment is extremely corrosive.
CODE SYMBOLS
1 2 3 4 5 6 7 8
F HF
9 10 11 12 13
14 15
Description
3
S
T
V
W
X
Connections
Process
connection
Oval flange
screw
Conduit
connection
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
7/16-20UNF
7/16-20UNF
M10 (or M12)*
M10 (or M12)*
7/16-20UNF
G 1/2
1/2-14NPT
Pg 13.5
M20×1.5
Pg 13.5
Span and materials
Static
pressure
[MPa]
{bar}
Span limit (*2)
[kPa]
(m bar)
Process
cover
Diaphragm
Wetted
cell body
–0.1 to +3.2
{–1 to +32}
0.1…1
{1…10}
316 stainless steel
316L stainless steel
316 stainless steel
–0.1 to +10
{–1 to 100}
0.6…6
{6…60}
316 stainless steel
316 stainless steel
Hast. C
316L stainless steel
Hast. C lining
316 stainless steel
316 stainless steel
Hast. C
Hast. C lining
33V
33H
33M
33T
35V
35H
35M
35T
36V
36H
36M
36T
38V
–0.1 to +16
{–1 to +160}
3.2…32
{32…320}
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316L stainless steel
Hast. C
Monel
Tantalum
316L stainless steel
Hast. C
Monel
Tantalum
316L stainless steel
Hast. C
Monel
Tantalum
316L stainless steel
316 stainless steel
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
43V
43H
43M
45V
45H
45M
46V
46H
46M
48V
–0.1 to +42
{–1 to +420}
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316L stainless steel
Hast. C
Monel
316L stainless steel
Hast. C
Monel
316 stainless steel
Hast. C
Monel
316 stainless steel
316 stainless steel
Hast. C lining
Monel lining
316 stainless steel
Hast. C lining
Monel lining
316 stainless steel
Hast. C lining
Monel lining
316 stainless steel
23B
23L
23U
25B
25L
25U
26B
26L
26U
–0.1 to +10
{–1 to+100}
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
Hast. C
Monel
Tantalum
Hast. C
Monel
Tantalum
Hast. C
Monel
Tantalum
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
11V
11H
22V
22H
Note:
13…130
{130…1300}
50…500
{500…5000}
300…3000
{3000…30000}
3.2…32
{32…320}
13…130
{130…1300}
50…500
{500…5000}
300…3000
{3000…30000}
3.2…32
{32…320}
13…130
{130…1300}
50…500
{500…5000}
* (1) The thread is M12, if 42MPa {420bar} static pressure is specified.
5
FHF...3
1 2 3 4 5 6 7 8
FHF
9 10 11 12 13
14 15
Description
3
A
B
D
J
E
F
H
K
L
Q
A
B
C
D
E
M
N
H
J
K
P
R
T
Q
A
B
C
D
E
F
Indicator and arrester
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, custom scale
None
Analog, double scale
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, custom scale
Yes
Analog, double scale
Yes
Digital, 0 to 100% of flow
None
Digital, 0 to 100% of flow
Yes
Approvals for hazardous locations (Approval pending)
None (for ordinary locations)
JIS, Flameproof (Conduit seal)
(Available for 4th digit code “S“)
JIS, Flameproof (Cable gland seal)
(Available for 4th digit code “S“)
FM, Flameproof (or explosionproof)
(Available for 4th digit code “T“)
CSA, Flameproof (or explosionproof) (Available for 4th digit code “T“)
BASEEFA, Flameproof (Conduit seal)
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)
FM, Intrinsic safety and nonincendive
CSA, Intrinsic safety and nonincendive
CENELEC, Intrinsic safety
CENELEC, Intrinsic safety and BASEEFA, Type N
SAA Flameproof (Conduit seal)(Available for 4th digit cord (“S,T,W)
SAA Intrinsic safety (Available for 4th digit cord (“S,T,W)
SAA Type–N (non-sparking)(Available for 4th digit cord (“S,T,W)
Side vent/ drain and mounting bracket
Side vent/drain
Mounting bracket
None
None
Specify "A", "B", or "C" for the
None
Yes, carbon steel
7th digit code "B", "L", or "U"
None
Yes, stainless steel
Yes
None
Yes
Yes, carbon steel
Yes
Yes, stainless steel
Stainless steel parts
Stainless steel tag plate
Stainless steel elec, housing
Coating of cell
None
None
None
Yes
None
None
None
Yes
None
Yes
Yes
None
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
Special applications and fill fluid
Treatment
Fill fluid
None (standard)
Silicone oil
None (standard)
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (Material code "W", "V")
Chlorine service
Fluorinated oil (Material code "H", "T", "B", "U")
NACE specification
Silicone oil (Not available for 7th digit code "T", "U" and 15th digit code "A", "B")
Vacuum service
Silicone oil for vacuum use
Sensor O-ring
Viton
Teflon
Bolt/nut
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
(*2)
NACE bolt/nut (ASTM A320 L7M/A194 2HM)
304 stainless steel/304 stainless steel
} (*3)
(*5)
630 stainless steel/304 stainless steel
} (*4)
}
Y
B
C
E
M
N
P
Q
Y
W
G
A
D
N
R
A
B
A
B
C
D
E
F
}
}
Notes: (*2) Static pressure should be –0.1 to +10MPa{–1 to +100bar}.
(*3) Available for the 5th digit code "1", "2", "3". In case of stainless steel bolt
with the 5th digit code "3", static pressure should be –0.1 to +10MPa {–1 to + 100bar}.
(*4) Available for the 5th digit code "3", "4".
(*5) In case of tropical use, select a stainless bolts and nuts.
6
OUTLINE DIAGRAM (Unit:mm)
Fastener
(In case of 10th
digit code “B,C,M,N“)
Vent/drain plug
(When the vent/drain plug attatched on
the upper side of the detector)
Zero/span ADJ. screw
In case of 4th
digit code
“S,V,W,X“
Mtg. Pipe
JIS 50A (2")
70
50
126.5
110
Up
43.5
ø80
104
“A“
Press. conn.
88
Down
38
“B“
Conduit conn.
37
120
242
With field ind.
(option)
51
71
U - Bolt M8
4 Holes
9 dia.
Vent/drain plug
Cable gland (option)
see note
58
“C“
Conduit conn.
(27)
Earth terminal
(both side )
see table1
Detail “A“
(press conn.)
Detail “C“
DETAIL “B“
(Conduit conn.)
Ø80
ø18.5
ø13
ø 15
41.3
Side vent
(option)
270
E
17
8
Oval flange
screw
see table1 1
F
2.5
H
L.P.
ø7
G 1/2
D
H.P.
See table 1
see table 1
2-M8 × 12
4th digit
code
Conduit conn.
D
E
F
Press. conn.
H
S
G1/2
54
T
1/2
16 5
–14NPT
1/4–18NPT
70
V
Pg13.5
1/4–18NPT
W
M20 × 1.5 16 5
54
104
CONNECTION
DIAGRAM
+
–
X
CK+ CK–
Pg13.5
17 8
8
8
4.5
4.5
Rc1/4
1/4–18NPT
1/4–18NPT
Oval flange
screw
7/16-20UNF
Screw depth13
7/16-20UNF
Screw depth13
M10
Screw depth13
7M10
Screw depth13
7/16-20UNF
Screw depth13
Earth
terminal
M4
No. 8-32UNC
M4
M4
M4
Table 1
+ –
Note1) : Cable gland is supplied in case of flamproof packing type.
ø11 cable is suitable.
S
T
FHF V
W
X
W
V
H 3
M
T
7
FHF...3
U - Bolt M8
Mtg.pipe
JIS 50A (2")
41.3
Up
50
70
110
43.5
Oval fgange
screw see table 1
φ80
104
Fastener
(In case of 10th
digit code
“B,C,M,N“)
“A“ or “B“
press conn.
In case of 4th
digit code
“S,V,W,X“
Zero/span ADJ. screw
88
Down
38
“C“
Conduit conn.
40
71
Vent/drain plug
“B“
Conduit conn.
Cable gland (option)
see note
With field ind
(option)
51
4 Holes
9 dia.
245
120
Earth terminal
(both side)
see table 1
58
Detail “B“
4th digit code
“T,V,W,X“
Detail “A“
(Press. conn.“)
4th digit code “S“
φ16
(27)
φ16
+0.2
2 -0.1
φ12 +0.1
10
φ80
1
0
1/4-18NPT
273
φ4
φ4
Detail “C“
(Conduit conn.)
L.P.
Detail “D“
φ13
φ15
H.P.
F
17
H
4-M8 × 12
54
E
70
See table 1
104
CONNECTION
DIAGRAM
+
–
CK+ CK–
+ –
G 1/2
4th digit
coode
S
T
FHF V 2
W
X
B
L 3
U
G1/2
T
1/2
-14NPT
V
Pg13.5
W
M20 × 1.5
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan
Phone: 81-3-5435-7111
http://www.fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm
Pg13.5
F
17
16
8
16
8
H
Earth
terminal
Oval flange
screw
8
7/16–20UNF
Screw depth 13
5
7/16–20UNF
Screw depth 13
M4
No. 8-32UNC
5
M10
Screw depth 13
M10
Screw depth 13
M4
4.5
7/16–20UNF
Screw depth 13
M4
4.5
M4
Table 1
φ11 cable is suitable.
Head office
E
S
X
Note) : Cable gland is supplied in case of flameproof packing type.
Conduit conn.