FUJI EDSX6-107

FCX – AX SERIES
FLOW TRANSMITTER
Hydroseal® Diaphragm Version
FHF...3
DATA SHEET
FEATURES
1. Unique hydroseal diaphragm
Permeation of hydrogen into the detecting unit through
seal diaphragm can be suppressed thanks to the unique
seal diaphragm (double coating) which employs coating
of gold and ceramic.
Micro Capacitance
Silicone sensor
Base material
(SUS316L)
Process
cover
Sensor
unit
Ceramics
coating
Gold
coating
Sealing diaphragm
coated with gold
and ceramics
SPECIFICATIONS
2. High accuracy
± 0.15% accuracy for all calibrated spans is the standard
feature for flow transmitter covering 3.2 to 130kPa (or,
320 mmH2O to 13 mH2O). Fuji’s Micro-capacitance
silicon sensor assures feature.
3. Minimum environment influence
Fuji's patented "Advanced Floating Cell" design which
protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications.
4. Application flexibility
Various option that render the FCX-AX series suitable
for almost any process applications include.
— Analog indicator at either the electronics side or terminal side
— Full range of hazardous location approvals
— 4 12 -digit LCD meter
— Stainless steel electronics housing
— Built-in RFI filter and lightning arrester
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Type
Span limit [kPa]
{mbar}
Static pressure
[MPa] {bar}
F
F
C
C
33
35
–0.1
(–1
–0.1
(–1
to
to +
to
to +
16)
160)
16)
160)
Min.
(
(
3.2 )
32
)
13
130
)
Range limit
Max.
[kPa] {m bar}
32) +/–
(
320) (+/–
130)
+/–
(
1300) (+/–
32 1
320)
130))
1300)
–
Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
temperature below 60°C.
– The maximum span of each sensor can be converted to
different units using below factors.
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
Overrage limit: To maximum static pressure limit
EDSX6-107
Date
Mar. 15, 1999
FHF...3
Output signal:
4 to 20mA DC
Square root of diffential input pressure
between 0.5% and 100% input.
Linear or zero is selectable below 0.5%
of input.
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
Load limitations: see figure below
[Ω]
Load resistance
2000
1533Ω
1500
1000
600Ω
Operating
area
500
24V
250
10
16.1
10.5V
Power voltage
45V
50
[V]
Hazardous locations: (Approval pending)
Authorities
BASEEFA
Factory
Mutual
CSA
RIIS
SAA
Flameproof
Ex ds IIC T5, T6
Class I II III
Div. 1
Groups B thru. G
Class I II III
Div. 1
Groups C thru. G
Ex ds IIB+H2 T4
Ex d II C T5, T6
IP 66/67
Intrinsic safety
EEx ia IIC T4, T5
Class I II III
Div. 1
Groups A thru. F
Class I II III
Div. 1
Groups A thru. G
—
Ex ia II C T5, T6
IP 66/67
Type N
Nonincendive
Ex N II T5
Class I II III
Div. 2
Groups A thru. G
Class I II III
Div. 2
Groups A thru. G
—
Ex n II C T5, T6
IP 66/67
Zero/span adjustment:
Zero is adjustable from the external adjustment screw.
The adjustment screw can also function
to adjust span when MODE SWITCH (located on the electronics unit) is in the
span mode.
INHIBIT mode to disable the adjustable
screw is also available.
Damping:
Adjustable electrical damping.
The time constant is adjustable to 0, 0.3,
1.2, 4.8, or 19.2 seconds.
Zero elevation/suppression:
–100% to +100% of URL
Normal/reverse action:
Selectable by moving a jumper pin located on the electronics unit.
Indication:
Analog indicator or 4 12 -digit LCD meter,
as specified.
Burnout direction: If self-diagnostic detect transmitter failure, the analog signal will be driven to
either “Output Hold”, “Output
Overscale” or “Output Underscale”
modes.
Model FHF: Unless otherwise specified in the order,
the transmitter will be shipped in “Output Hold” mode.
(Output signal just before failure happens is maintained.)
2
“Output Hold”: Output signal is hold as the value just
before failure happens.
“Output Overscale”: Approx. 21.6mA
“Output Underscale”: Approx. 3.8mA
3.2
3.8 4
20 20.8
Over scale
Burnout
0
Normal operating range
Under scale
Probable under range
Burnout
21.6
Probable over range
Loop-check output:
Transmitter can output constant signal of
4mA, 12mA, or 20mA if MODE SWITCH
is set to the loop check mode.
Temperature limit: Ambient: – 40 to + 85°C
(– 20 to + 80°C for LCD indicator)
(– 40 to + 60°C for arrester option)
(– 10 to + 60°C for fluorinated oil fill
transmitter)
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified in
each standard.
Process: – 40 to +120°C for silicone fill
sensor
– 20 to +80°C for fluorinated oil fill sensor
Storage: – 40 to +90°C
Humidity limit:
0 to 100% RH
Performance specifications
Accuracy rating: Output 50 to 100%: 0.15% of span
Output 20 to 50%: 0.375% of span
Output 10 to 20%: 0.75% of span
(Including linearity, hysteresis, and repeatability)
Stability:
± 0.15% of upper range limit (URL) for 24
months
Temperature effect:
Effects per 28°C change between the limits of – 40°C and +85°C
Shift at 20% output
(% of URL)
Range code
(6th digit in "Code symbols")
“3”/ 32kPa {320m bar} max. span
“4”/ 64kPa {640m bar} max. span
“5”/ 130kPa {1300m bar} max. span
± 0.25+0.19 URL %/28°C
Span
(
)
Static pressure effect:
Static pressure code
(5th digit in "Code symbols")
Shift at 20% output
(% of URL)
± 0.375%/10MPa{100bar}
“3”
Overrange effect: Shift at 20% output (% of URL)
Static pressure code
(5th digit in "Code symbols")
Shift at 20% output
(% of URL)
± 0.75% / 16MPa {160bar } (*1)
“3”
1
(* ) in case of 6th code “5”.
Supply voltage effect:
Less than 0.05% of calibrated span per
10V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Step response: (without electrical damping)
FHF
FHF 4,
Time constant
3
0.45 s
5
0.2 s
Dead time
approx. 0.3 s
Mounting position effect:
Zero shift, less than 0.12kPa {1.2m bar} for
a 10° tilt in any plane.
No effect on span.
This error can be corrected by adjusting
Zero.
(Double the effect for fluorinated fill sensors)
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
Physical specifications
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
Meets DIN 19213.
Process-wetted parts material:
Material
code
(7th figure Process cover
in "Code
symbols")
C
316 stainless
steel(*1)
Diaphragm
Wetted
sensor body
Optional features
Indicator:
A plug-in analog indicator (1.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
1
An optional 4 2 digits LCD meter is also
available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity : 4KV (1.2 x
50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
ASTM B7M or L7M bolts and 2HM nuts
(Class II) are available.
Static pressure rating for code “3” (160
bar) is degraded to 100 bar.
Vacuum service: Special silicone oil and filling procedure
are applied.
See below figure.
Vent/drain
Sealing liquid:Silicone oil (Code:Y,G,N)
Sealing liquid:Silicone oil (Code:R)
316L stainless 316 stainless
steel(*2)
steel
316 stainless
steel
Notes: * (1) SCS14 per JIS G 5121
(2) The diaphragm face is coated with gold and ceramic.
Remark: Sensor O-rings: Viton and teflon selectable.
Availability of above material design depends on ranges and static
pressure. Refer to “Code symbols”.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy (standard), finished
with epoxy/polyurethane double coating, or 304 stainless steel, as specified.
Bolts and nuts: Cr-Mo alloy (standard), 304
stainless steel (for static pressure code
“1”, “2”, and “3” only), or 630 stainless steel (for static pressure code "4"
only). Static pressure rating for code
“3” with 304 stainless steel bolts is degraded to 10MPa{100bar}.
Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil)
Mounting bracket: Carbon steel with epoxy coating or 304 stainless steel, as
specified
[kPa abs]
{mbar abs}
101
{1010}
Operating pressure
Type
Environmental protection:
IEC IP67 and NEMA 4X
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting, or direct
process mounting.
Mass{weight}:
Transmitter approximately 4.4kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
53.3
{533}
Operating
area
6.7
{67}
2.7
{27}
–40
–15
60 85 120
Process temperature[°C ]
Fig. 1 Relation between process temperature and
operating pressure
3
FHF...3
Customer tag:
Coating of cell:
A stainless steel tag with customer tag
data is wired to the transmitter.
Cell's surface is finished with epoxy/
polyuretane double coating.
Specify if environment is extremely corrosive.
ACCESSORIES
Oval flanges:
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Three-value manifolds:
(Model FFN, refer to Data Sheet No.
EDS6-10)
Available in carbon steel or in 316 stainless steel and in pressure rating 16MPa
{160bar} or 42MPa{420bar}.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510412. The applicable standards used to demonstrate
compliance are :EMI (Emission)
EN50081-1 : 1992
Test item
Frequency range
Basic standard
Applicable Electromagnetic Radiation
Disturbance
30-1000MHz
EN55022
Class B
EMS (Immunity)
EN50082-1 : 1992
No.
Test item
Test
specification
Basic
standard
Performance
criteria
1
Electrostatic
discharge
8kV (Air)
IEC 801-2:1984
B
2
Radio-frequency 27-500MHz
electromagnetic 3V/m
IEC 801-3:1984
field.
(Unmodulated)
A
3
Fast transients
common mode
0.5kV, 5/50
(Tr/Th) ns
5kHz Rep.
IEC 801-4:1988
B
"LVD - The transmitter is not covered by the requirements
of the LVD standard."
4
CODE SYMBOLS
1 2 3 4 5 6 7 8
F HF
9 10 11 12 13
14 15
Description
3
S
T
V
W
X
Connections
Process
connection
Oval flange
screw
Conduit
connection
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
7/16-20UNF
7/16-20UNF
M10
M10
7/16-20UNF
G 1/2
1/2-14NPT
Pg 13.5
M20×1.5
Pg 13.5
Span and materials
Static
pressure
[MPa]
{bar}
–0.1 to +16
{–1 to +160}
33C
Span limit (*2)
[kPa]
(m bar)
3.2…32
{32…320}
Process
cover
Diaphragm
Wetted
cell body
316 stainless
steel
316L stainless
steel (*1)
316 stainless
steel
13…130
{130…1300}
35C
A
B
C
D
J
E
F
G
H
K
L
Q
A
B
C
D
E
M
N
G
H
J
K
P
R
T
Q
A
B
C
D
E
F
Indicator and arrester
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, 0 to 100% sq. root scale
None
Analog, custom scale
None
Analog, double scale
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, 0 to 100% sq. root scale
Yes
Analog, custom scale
Yes
Analog, double scale
Yes
Digital, 0 to 100%
None
Digital, 0 to 100%
Yes
Approvals for hazardous locations (Approval pending)
None (for ordinary locations)
JIS, Flameproof (Conduit seal)
JIS, Flameproof (Cable gland seal)
FM, Flameproof (or explosionproof)
CSA, Flameproof (or explosionproof)
BASEEFA, Flameproof (Conduit seal)
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)
JIS, Intrinsic safety
FM, Intrinsic safety and nonincendive
CSA, Intrinsic safety and nonincendive
CENELEC, Intrinsic safety
CENELEC, Intrinsic safety and BASEEFA, Type N
SAA Flameproof (Conduit seal)(Available for 4th digit code "S,T,W")
SAA Intrinsic safety (Available for 4th digit code "S,T,W")
SAA Type–N (non-sparking)(Available for 4th digit code "S,T,W")
Side vent/ drain and mounting bracket
Side vent/drain
Mounting bracket
None
None
None
Yes, carbon steel
None
Yes, stainless steel
Yes
None
Yes
Yes, carbon steel
Yes
Yes, stainless steel
Notes: * (1) The diaphragm face is coated with gold and ceramic.
5
FHF...3
1 2 3 4 5 6 7 8
FHF
9 10 11 12 13
14 15
Description
3
Stainless steel parts
Stainless steel tag plate
None
Yes
None
Yes
None
Yes
None
Yes
Y
B
C
E
M
N
P
Q
Y
W
G
A
N
A
B
A
B
C
D
E
Stainless steel elec, housing
None
None
Yes
Yes
None
None
Yes
Yes
Coating of cell
None
None
None
None
Yes
Yes
Yes
Yes
Special applications and fill fluid
Treatment
Fill fluid
None (standard)
Silicone oil
None (standard)
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (Material code "W", "V")
NACE specification
Silicone oil (Not available for 7th digit code "T", "U" and 15th digit code "A", "B")
Sensor O-ring
Viton
Teflon
Bolt/nut
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
(*2)
NACE bolt/nut (ASTM A320 L7M/A194 2HM)
}
304 stainless steel/304 stainless steel
} (*3)(*4)
Notes: (*2) Static pressure should be –0.1 to +10MPa{–1 to +100bar}.
(*3) Available for the case of stainless steel bolt
with the 5th digit code "3", static pressure should be –0.1 to +10MPa {–1 to + 100bar}.
(*4) In case of tropical use, select a stainless bolts and nuts.
6
OUTLINE DIAGRAM (Unit:mm)
Fastener
(In case of 10th
digit code “B,C,M,N“)
Vent/drain plug
(When the vent/drain plug attatched on
the upper side of the detector)
Zero/span ADJ. screw
In case of 4th
digit code
“S,V,W,X“
Mtg. Pipe
JIS 50A (2")
70
50
126.5
110
Up
43.5
ø80
104
“A“
Press. conn.
88
Down
38
“B“
Conduit conn.
37
120
242
With field ind.
(option)
51
71
U - Bolt M8
4 Holes
9 dia.
Vent/drain plug
Cable gland (option)
see note
58
“C“
Conduit conn.
(27)
Earth terminal
(both side )
see table1
Detail “A“
(press conn.)
Detail “C“
DETAIL “B“
(Conduit conn.)
Ø80
ø18.5
ø13
ø 15
41.3
Side vent
(option)
270
E
17
8
Oval flange
screw
see table1 1
F
2.5
H
L.P.
ø7
G 1/2
D
H.P.
See table 1
see table 1
2-M8 × 12
4th digit
code
F
Press. conn.
H
S
G1/2
54
T
1/2
16 5
–14NPT
1/4–18NPT
70
V
Pg13.5
1/4–18NPT
W
M20 × 1.5 16 5
X
Pg13.5
54
104
CONNECTION
DIAGRAM
+
Conduit conn.
D
E
–
17 8
8
8
4.5
4.5
Rc1/4
1/4–18NPT
1/4–18NPT
Oval flange
screw
7/16-20UNF
Screw depth13
7/16-20UNF
Screw depth13
M10
Screw depth13
7M10
Screw depth13
7/16-20UNF
Screw depth13
Earth
terminal
M4
No. 8-32UNC
M4
M4
M4
Table 1
CK+ CK–
+ –
Note1) : Cable gland is supplied in case of flamproof packing type.
ø11 cable is suitable.
S
T
FHF V
W
X
C 3
7
FHF...3
Head office
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan
Phone: 81-3-5435-7111
http://www.fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202
Fax: 81-42-585-6187, 6189
Information in this catalog is subject to change without notice.
Printed in Japan