FCX – AX SERIES SMALL FLANGE REMOTE SEAL TYPE DIFFERENTIAL PRESSURE TRANSMITTER FHX, FKX...3 DATA SHEET The FCX –AX Series small flange remote seal type differential pressure transmitter accurately measures differential pressure, liquid level or gauge pressure and transmits a proportional 4 to 20mA signal. The trans-mitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. Totally welded construction of the seals assures excellent reliability in high temperature and highly corrosive process conditions. FEATURES 1. Directly connectable to 1-1/2in and 2in flanges The transmitter is connectable to 1-1/2in and 2in pipes without a reducer. 2. Flow measurement without impulse piping 1/2in and 3/4in flange size is also available. This differential pressure transmitter allows connection to 1/2in and 3/4in flanges of a general size for the orifice tap, which eliminates the need of using a impulse piping. Problems with the impulse piping, such as clogging, leaks or corrosion can be solved. In addition, the following process connection is also available. Screw connection 1/2-14NPT, 3/4-14NPT, Rc1/2, Rc3/4 3. Minimum environmental influence The "Advanced Floating Cell" design which protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications. 4. Replaceable Communication Module Fuji micro-electronics manufacturing technology offers replaceable communication module that makes FCX–AX transmitter very unique in design. In case of change in communication protocl all that needs to be done is just replace the module and the transmitter gets upgraded to the new version. 5. Fuji/HART bilingual communication module The communication module is "bilingual" to speak both Fuji proprietary protocol and HART. Any HART compatible devices can communicate with FCX–AX series transmitters. 6. Application flexibility Various options that render the FCX–AX suitable for almost any process applications include: – Analog indicator at either the electronics side or terminal side – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 4 1/2 -digits LCD meter – Stainless steel electronics housing – Wide selection of materials – High temperature, high vacuum seals 7. Programmable output Linearization Function In addition to Linear and Square Root, output signal can be freely programmable. (Up to 14 compensated points at approximation.) (Available for amplifier unit from version 24 and FXW(HHC) version 5.3.) 8. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW hand Held Communicator (HHC) to comply with NAMUR NE43. (Available for amplifier unit from version 24 and FXW (HHC) version 5.3.) 9. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. SPECIFICATIONS Functional specifications Type: Model FHX: 4 to 20mA Model FKX: 4 to 20mA with digital signal Service: Liquid, gas, or vapour Static pressure, span, and range limit: Span limit [kPa] (m bar} Type FHX F F X X 5 Up tp } flange rating 6 { { Range limit [kPa] {m bar} Max. Min. Static pressure FKX 13 3 130 } { 30} 50 12.5 500 } {125} FHX/FKX { { 130 1300 } 500 5000 } +/– { +/– +/– { +/– 130 1300 } 500 5000 } – Maximum static pressure limit for screw connction type: 4.2MPa EDSX6-103 Date Mar. 10, 1999 FHX, FKX...3 – Lower limit of static pressure (vacuum limit), Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: Atmospheric pressure – The maximum span of each sensor can be converted to different units using factors as below. 1MPa=103kPa=10bar=10.19716kgf/cm2= 145.0377psi 1kPa=10mbar=101.976mmH2O=4.01463H2O Overrage limit: To maximum static pressure limit Output signal: Model FHX: 4 to 20mA DC 2-wire, linear signal Model FKX: 4 to 20mA DC (linear or square root) with digital signal superimposed on the 4 to 20mA signal Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below [Ω] Load resistance 2000 1533Ω 1500 1000 600Ω 3.2 Operating area 500 24V 250 10 16.1 10.5V Power voltage BASEEFA Factory Mutual Flameproof Ex ds IIC T5, T6 Class I II III Div. 1 Groups B thru. G Exds IIB + H2 T4 50 [V] Intrinsic safety EEx ia IIC T4, T5 Class I II III Div. 1 Groups A thru. F — Type N Nonincendive Ex N II T5 Class I II III Div. 2 Groups A thru. G — Zero/span adjustment: Model FHX: Zero is adjustable from the external adjustment screw. The adjustment screw can also function to adjust span when MODE SWITCH (located on the electronics unit) is in the span mode. INHIBIT mode to disable the adjustment screw is also available. Model FKX: Zero and span are adjustable from the HHC. Zero is also adjustable externally from the adjustment screw. Damping: Adjustable electrical damping. Model FHX: The time constant is adjustable to 0, 0.3, 1.2, 4.8, or 19.2 seconds. Model FKX: The time constant is adjustable between 0 to 38.4 seconds. Zero elevation/suppression: –100% to +100% of URL 2 20 20.8 Over scale Burnout Hazardous locations: (Approval pending) Authorities 3.8 4 45V Note: For communication with HHC (Model: FXW), min. of 250Ω required. RIIS Normal/reverse action: Model FHX: Selectable by moving a jumper pin located on the electronics unit. Model FKX: Selectable from HHC Indication: Analog indicator or 4 1/2 digit LCD meter, as specified. Burnout direction: If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. Model FHX: Unless otherwise specified in the order, the transmitter will be shipped in “Output Hold” mode. (Output signal just before failure happens is maintained.) Model FKX: Selectable from HHC “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Approx. 21.6mA (Adjustable within the range 20.8mA to 21.6mA from HHC) “Output Underscale”: Approx. 3.8mA (Adjustable within the range 3.2mA to 3.8mA from HHC) 0 Normal operating range Under scale Probable under range Burnout 21.6 Probable over range Loop-check output: Model FHX: Transmitter can output constant signal of 4mA, 12mA, or 20mA if MODE SWITCH is set to the loop check mode. Model FKX: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC. Temperature limit: Ambient: – 15 to + 65°C (– 15 to + 60°C for arrester option) (– 10 to + 60°C for fluorinated oil fill transmitter) (– 10 to + 60°C for silicone oil "H", "S") For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Process: Fill fluid 13th digit of "Code symbols" Fluorinated oil W, A and D Silicone oil H Y and G S Storage: – 40 to +70°C Humidity limit: 0 to 100% RH Process temperature – 20 to 120°C 0 to 250°C – 40 to 120°C 0 to 250°C Lower limit of static press. Atmospheric pressure 2.7kPa abs {20mmHg abs} Communication: (Model FKX only) With HHC (Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured. Items Display Set Tag No. v v Model No. v v Serial No. v — Engineering unit v v Range limit v — Measuring range v v Damping v v Output mode v v Burnout direction v v Adjustment v v Output adjust — v Data v — Self diagnoses v — Printer — — External switch lock v v Transmitter display(*) v v Linearise (**) v v Rerange (**) v v Notes:(*) HHC's version must be more than 5.0 1– 2), to use this (or FXW function. (**) HHC's version must be more than 5.3, and Amplifier unit version 24. Programmable output linearization function: In smart version, output signal can be characterized with “14 points linear approximation function” from HHC. Performance specifications Accuracy rating: (including linearity, hysteresis, and re(Standard) peatability) For spans greater than 1/10 of URL: 0.25% of span For spans below 1/10 of URL (Model FKX only): 0.1 x URL ± 0.17+0.08 % of span Span (Option) For spans greater than 1/10 of URL: 0.1% of span For spans below 1/10 of URL (Model FKX only): 0.1 x URL ± 0.05+0.05 % of span Span Linearity: 0.1% of calibrated span Stability: ± 0.2% of upper range limit (URL) for 24 months Temperature effect: Effects per 28°C change between the limits of – 15°C and +65°C Zero shift: ± 0.5%/28°C (x equal to 1/2 URL or more) URL Zero shift; ± (0.5 )%/28°C 2xx (x less than 1/2 URL) Total shift; ± 0.75%/28°C (x less than 1/2 URL or more) URL Total shift; ± (0.25 + 0.5 )%/28°C 2xx (x less than 1/2 URL) High performance type (option) Zero shift: ± 0.5%/28°C (x equal to 1/6.5 URL or more) URL Zero shift; ± (0.5 )%/28°C 6.5 x x (x less than 1/6.5 URL) Total shift; ± 0.75%/28°C (x equal to 1/6.5 URL or more) URL Total shift; ± (0.25 + 0.5 )%/28°C 6.5 x x (x less than 1/6.5 URL) Where, x: Calibrated span ( ) ( ) URL: Maximum span (Upper Range Limit) Note 1: Condition: Capillary length: 3m max. In case the capillary length is 5m, the performance becomes 1.5 times worse than above. Note 2: In case the 7th code (material code) is other than W, A, B, C or D, the performance becomes 2.5 times worse than above. Note 3: Above specifications are based on the conditions that flanges and sensor unit are at the same temperature and in the same level. If temperature is different at flanges, capillary or sensor unit, output variation may increase. 3 FHX, FKX...3 Static pressure effect: Zero shift; 0.2% of URL/1MPa (10 bar) 2.5 times the zero shift for material code, "H", "M" and "T" +0.2 Span shift: – 0.2 –0.1 % of calibrated span for flange nominal pressure Overrange effect: Zero shift; 0.3% of URL for flange nominal pressure 2.5 times the effects for material code. "H", "M" and "T" Supply voltage effect: Less than 0.05% fo calibrated span per 10V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. Step response: (without electrical damping) Time constant (*) 1.7 s Dead time Approx. 0.3 s Note: * Capillary length: 1.5m, Ambient temperature: 23°C Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ/500V DC. Turn-on time: 4 sec. Internal resistance for external field indicator: 12Ω or less 4 Physical specifications Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5 conduit, as specified. Process connections: JIS 10K, 20K, 30K - 40, 50A 10K, 20K, 30K - 15, 20A (with Adapter) ANSI/JPI 150LB, 300LB -11/2 ", 2" 150LB, 300LB - 1/2", 3/4" (with Adapter) Screw connection (with Adapter); Rc1/2, Rc3/4, 1/2 - 14NPT, 3/4 - 14NPT Diaphragm extension: 0, 50, 100, 150, or 200mm as specified. (See model code. Extended diaphragm is available only with 316L stainless steel diaphragm) Process-wetted parts material: Diaphragm: 316L stainless steel, Hastelloy-C, Monel or Tantalum Flange face: 316 stainless steel, HastelloyC lining Monel lining, or Tantalum lining Extension: 316 stainless steel Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy (standard), finished with polyester coating, or 316 stainless steel (SCSI4 par JIS G51), as specified. Capillary: In case of 13th code "Y. W. G. A. D", PVC armored stainless steel. In case of 13th code "H. S", stainless steel armored stainless steel. Mounting flange: (option) 304 stainless steel or carbon steel Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil) Mounting bracket: Carbon steel with epoxy coating or 304stainless steel, as specified Environmental protection: IEC IP67 and NEMA 4X Mounting: On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting Mass {weight}: Transmitter approximately 15kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option 4.5kg for stainless steel housing option 1.5kg per 50mm extension of diaphragm Optional features ACCESSORIES Indicator: A plug-in analog indicator (1.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 41/2 digits LCD meter is also available. Arrester: A built-in arrester protects the electronics from lightning surges. Lighting surge immunity is 4kV (1.2 x 50µs). Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: Oil-free procedures as above. Includes fluorinated oil for fill. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. Vacuum service: Special silicone oil and filling procedure are applied. See below figure. Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) Communication module: (standard for model FKX) By adding communication module, remote setting function becomes available for model FHX. Remark: When the communication module is connected, the operation mode of external zero/span adjustment screw is limited to zero adjustment only. Filled liquid: Silicone (Code Y,G) [kPa abs] {m bar abs} Silicone (Code S) Operating pressure 101 {1010} 53.3 {533} Operating area 13.3 {133} Non-operating area 2.7 {27} –40 0 60 85 120 Process temperature 200 230 250 [°C ] Fig. 1 Relation between process temperature and operating pressure Customer tag: Coating of cell: A stainless steel tag for customer tag data is wired to the transmitter. Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive. 5 FHX, FKX...3 CODE SYMBOLS 1 2 3 4 5 6 7 8 F X 3 9 10 11 12 13 14 15 16 17 18 19 20 Description 0 Type 4 to 20mA, Output type 4 to 20mA with digital signal, Output type FHX FKX Conduit connection <4th digit> G 1/2 1/2 - 14NPT Pg 13.5 M20 X 1.5 S T V W Flange <5th digit> Material Size and rating 304 stainless JIS 10K 40A steel JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" Carbon steel JIS 10K 40A JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" None 40A, 1 1/2B (Wafer type) 50A, 2B Direct mounting adapter connection (* 1) 0 1 2 3 4 5 A B C D G H J K L M Q R S T W X Y Span limit [kPa] {m bar} <6th digit> FHX FKX 13...130 (130...1300) 3...130 ( 30...1300) 50...500 (500...5000) 12.5...500 (125...5000) 5 6 Material/diapharagm extension <7th digit> Diaphragm Flange face W A B C D 316L stainless steel 316 stainless steel H M T Hastelloy-C Monel Tantalum Hastelloy-C Monel Tantalum Note 1: Direct mounting adapter type is specified at 16th to 20th digit. Direct mounting adapter is available only for 7th digit code "W". 2: Diaphragm extension is available only for 2" (50A) flanges. 6 Diaphragm extension (mm) 0 50 100 150 200 0 0 0 (* ) 2 1 2 3 4 5 6 7 8 F X 9 10 11 12 13 14 15 16 17 18 19 20 Description 3 Indicator and arrester <9th digit> Indicator None Analog, 0 to 100% linear scale Analog, 0 to 100% sq. root scale Analog, custom scale Analog, double scale None Analog, 0 to 100% linear scale Analog, 0 to 100% sq. root scale Analog, custom scale Analog, double scale Digital, 0 to 100% Digital, custom scale Digital, 0 to 100% square root Digital, 0 to 100% Digital, custom scale Digital, 0 to 100% square root A B C D J E F G H K L P M Q S N Arrester None None None None None Yes Yes Yes Yes Yes None None (Model FKX only) None Yes Yes (Model FKX only) Yes Approvals for hazardous locations <10th digit> (Approval pending) None (for ordinary locations) JIS, Flameproof (Conduit seal) (Available for 4th digit code "S") JIS, Flameproof (Cable gland seal) (Available for 4th digit code "S") FM, Flameproof (or explosionproof) (Available for 4th digit code "T") BASEEFA, Flameproof (Conduit seal) BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only) FM, Intrinsic safety and Nonincendive CENELEC, Intrinsic safety CENELEC, Intrinsic safety and BASEEFA, Type N A B C D M N H K P Capillary and mounting bracket <11th digit> mounting bracket Capillary A B G Carbon steel 1.5m 3m 5m D E L Stainless steel 1.5m 3m 5m Stainless steel parts <12th digit> Stainless steel tag plate Stainless steel elec. housing None None Yes None None Yes Yes Yes None None Yes None None Yes Yes Yes Y B C E M N P Q Coating of cell None None None None Yes Yes Yes Yes Treatment/Fill fluid <13th digit> Y W G A D H S Y C Treatment Fill fluid None None Degreasing Oxygen service Chlorine service High temp. 250°C High temp. and vacuum (250°C) Silicone oil (for general use) Fluorinated oil Silicone oil Fluorinated oil (7th digit code "W", "A", "B", "C" and "D") Fluorinated oil (7th digit code "H" and "T") Silicone oil (7th digit code "W", "A", "B", "C" and "D") Silicone oil } Teflon membrane <14th digit> None Yes (7th digit code "W", "H", "M", and "T") Odering information 1. When odering this instrument, specify the output orientation (burnout direction) in case of abnormality in the transmitter. Unless otherwise specified, the output hold function is supplied. 2. When odering FKX, specify the output mode (linear or square root output). Unless otherwise specified, linear output is supplied. 3. When specifying the digital indicator/actual scale (codes P and S on 9th digit), specify the method indication (indicated value and unit). 7 FHX, FKX...3 Specifications of Direct Mounting Adapter {for 15, 20A (1/2, 3/4") connection} and others Note 1. When odering the instrument with direct mounting adapter, specify "Y" in the 5th digit of Code Symbol, and specify 16th digit to 20th digits. When odering the instrument without direct mounting adapter, nothing should be filled in the 16th to 20th digits. 2. Unless otherwise described in the specifications, leave the 21st digit blank. 1 2 3 4 5 6 7 8 F X 3 9 10 11 12 13 14 15 16 17 18 19 20 Description 0 1 1 2 2 3 3 1 1 2 2 S S S S Process connection (direct mounting adapter) <16th to 17 digit> JIS 10K 15A JIS 10K 20A JIS 20K 15A JIS 20K 20A JIS 30K 15A JIS 30K 20A ANSI/JPI 150LB 1/2" ANSI/JPI 150LB 3/4" ANSI/JPI 300LB 1/2" ANSI/JPI 300LB 3/4" Screw connection Rc1/2 Screw connection Rc3/4 Screw connection Rc1/2 - 14NPT Screw connection Rc3/4 - 14NPT 1 2 1 2 1 2 H T H T R 2 N T Material (direct mounting adapter) <18th digit> Adapter W Bolts/nuts (* 1) 316 Stainless Steel Cr-Mo steel/carbon steel Vent/drain (for direct mounting adapter) <19 th digit> Standard Long type G N 1 2 Gasket (for direct mounting adapter) <20th digit> Standard (Teflon) (Only Y, W, G, A and D can be specified on 13th digit). For high temperature (spiral gasket) (Only H and S can be specified on 13th digit). Note 1 For connection of transmitter receiving pressure unit and direct mounting adapter 8 OUTLINE DIAGRAM (Unit:mm) Fastener (In case of 10th digit code "B,C,M,N") In case of 4th digit code "S,V,W,X" Zero/span adj. screw Mtg. pipe JIS 50A (2") U - BOLT M8 50 70 110 Up φ80 104 2-M8 x 12 Down 88 28 38 "A" Conduit conn. 233 Cable ground (Option) See note Inner of gasket "B" Conduit. conn. 71 φ 48 φ 49 φ 84 φE φD N holes h dia. 4 holes 9 dia. 58 With field ind. (Option) 20 t L 270 Earth terminal (both side) See table 1 51 71 (27) Detail "A" Detail "B" φ 13 261 17 K M φ 80 (Conduit conn.) φ 15 J G1/2 See table 1 S S H.P. L.P. <Optional stainless steel tag> 5th digit of code symbols φ D φ E t N-φ h 75 62 70 120 20 Flange 0, G 140 105 36 4-19 JIS-10K-40A 1, H 155 120 36 4-19 JIS-10K-50A 2, J 140 105 38 4-19 JIS-20K-40A 3, K 155 120 38 8-19 JIS-20K-50A 4th digit of Code symbols Conduit conn. K M S G1/2 17 8 No. 8-32UNC 16 5 M4 4.5 M4 5 M4 4, L 160 120 42 4-23 JIS-30K-40A T 1/2-14NPT 5, M 165 130 42 8-19 JIS-30K-50A V Pg13.5 A, Q 127 98.4 ANSI/JPI-150LB-1 1/2" W M20x1.5 B, R 152 120.6 39.5 4-20 C, S 156 114.3 D, T 165 127 37.5 4-16 41 4-23 42.5 8-20 ANSI/JPI-150LB-2" ANSI/JPI-300LB-1 1/2" ANSI/JPI-300LB-2" 71 φ 84 φ 49 Note *: Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. 2-M6 screw depth 9 Inner of gasket 20 <Wafer type> Earth terminal J 8 16 Table 1 7th digit of Code symbols W, H, M, T L 11th digit of Capillary code symbols length S [mm] Mass approx. [kg] 0 14 to 19.5 A,D 1500 A 50 15 to 30.5 B, E 3000 B 100 15.5 to 31 G, L 5000 C 150 16 to 31.5 D 200 16.5 to 32 S H F KXT V W Note: In case of water type, flange is excluded from the scope of supply. Mount flange, referring to the view. CONNECTION DIAGRAM 3 + – CK + CK – + – 9 FHX, FKX...3 OUTLINE DIAGRAM (Unit:mm) Fastener (In case of digit code B,C,M,N") In case of 4th digit code "S,V,W,X" Zero/span adj. screw Mtg. pipe JIS 50A (2") U - bolt M8 70 110 50 φ 80 104 2-M8 x 12 Up Down 88 "B" Conduit conn. Cable ground (Option) See note "A" Conduit conn. 28 38 233 58 4 holes 9 dia. Specifications for instrument with direct mounting adapter 80 20 t N holes h dia. 270 (102) 25 φ 84 φF φE φD S Vent/drain plug (27) Long vent/drain plug (Added specification) Detail "A" With field ind. (Option) 261 (Conduit conn.) CONECTION DIAGRAM + Detail "B" φ 15 – CK+CK– φ 13 17 71 φ 80 51 K M Earth terminal (Both side) See table 1 +– J G1/2 See table 1 Table 1 62 70 120 4th digit of Code symbols 16th digit of 17th digit of Flange code symbols code symbols φ D φ E φ -F t N-φ h JIS-10K-15A 12 95 70 51 4-15 1 1 1 2 100 75 56 14 4-15 JIS-10K-20A 2 1 95 70 51 14 4-15 JIS-20K-15A 2 2 100 75 56 16 4-15 JIS-20K-20A 55 18 4-19 JIS-30K-15A 3 1 115 80 3 2 120 85 1 H 89 60.3 34.9 11.5 4-16 ANSI/JPI-150LB - 1/2" 1 T 98 69.9 42.9 13 4-16 ANSI/JPI-150LB - 3/4" 2 H 95 66.7 34.9 14.5 4-16 ANSI/JPI-300LB - 1/2" 2 T 117 82.5 42.9 16 4-20 ANSI/JPI-300LB - 3/4" 60 18 4-19 JIS-30K-20A Note *: Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. 10 Conduit conn. J K M Earth terminal S G1/2 T 1/2-14NPT 16 5 M4 V Pg13.5 M4 W M20x1.5 17 8 8 4.5 16 5 No. 8-32UNC M4 11th digit of Capillary code symbols length S [mm] A,D 1500 B, E 3000 G, L 5000 S H F KXT Y V W 3 1 2 3 Fastener (In case of 10th digit code B,C,M,N") In case of 4th digit code "S,V,W,X" Zero/span adj. acrew Mtg. pipe JIS 50A (2") U - bolt M8 50 70 110 Up φ 80 104 2-M8 x 12 Down "A" Conduit conn. "B" Conduit conn. 88 Cable gland (Option) See note 23 28 38 233 58 4 holes 9 dia. 20 S φ 84 Press. conn. "D" 270 Earth terminal (Both side) See table 1 51 71 25 (102) Long vent/drain plug (Option) Vent/drain plug (27) Specifications for instrument with direct mounting adapter (Screw connection type) φ 80 Withh field ind. (Option) CONNECTION DIAGRAM – CK+ CK– 261 + + – Detail "A" (Conduit conn.) Detail "B" φ 15 62 70 120 17 K M φ 13 J G1/2 See table 1 Table 1 Conduit conn. 4th digit of Earth terminal Code symbols J K M S G1/2 T 1/2-14NPT V Pg13.5 W M20x1.5 17 8 11th digit of Capillary code symbols length S [mm] No. 8-32UNC M4 16 5 A,D 1500 B, E 3000 G, L 5000 M4 8 4.5 M4 16 5 16th digit of code symbols 17th digit of code symbols Press. conn. "D" S R Rc 1/2 S N 1/2 - 14NPT S 2 Rc 3/4 S T 3/4 - 14NPT Note *: Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. S H F KXT Y V W 3 S 11 FHX, FKX...3 The product conforms to the requirements of the Electromagnetic compatibility Directive 89/336/EEC as detailed within the technical construction file number TN510412. The applicable standards used to demonstrate compliance are :EMI (Emission) EN50081-1 : 1992 Test item Frequency range Basic standard Applicable Electromagnetic Radiation Disturbance 30-1000MHz EN55022 Class B EMS (Immunity) EN50082-1 : 1992 No. Test item Test specification Basic standard Performance criteria 1 Electrostatic discharge 8kV (Air) IEC 801-2:1984 B 2 Radio-frequency 27-500MHz electromagnetic 3V/m IEC 801-3:1984 field. (Unmodulated) A 3 Fast transients common mode 0.5kV, 5/50 (Tr/Th) ns 5kHz Rep. IEC 801-4:1988 B "LVD - The transmitter is not covered by the requirements of the LVD standard." Head office 11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan Phone: 81-3-5435-7111 http://www. fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187, 6189 Information in this catalog is subject to change without notice. Printed in Japan